Product Manual
Table Of Contents
- Table of contents
- 1 Safety precautions
- 2 General description
- 3 Elektronikon controller
- 3.1 General description
- 3.2 Control panel
- 3.3 Icons used on the display
- 3.4 Main screen
- 3.5 Shut-down warning
- 3.6 Shut-down
- 3.7 Service warning
- 3.8 Scrolling through all screens
- 3.9 Calling up element and dew point temperatures
- 3.10 Digital inputs
- 3.11 Calling up running hours
- 3.12 Calling up motor starts
- 3.13 Calling up module hours
- 3.14 Calling up/resetting the service timer
- 3.15 Selection between Local, Remote or LAN control
- 3.16 Calling up/modifying CAN address control
- 3.17 Calling up/modifying IP, Gateway and Subnetmask
- 3.18 Calling up/modifying pressure band settings
- 3.19 Modifying pressure band selection
- 3.20 Calling up/modifying service timer settings
- 3.21 Calling up/modifying unit of temperature
- 3.22 Calling up/modifying unit of pressure
- 3.23 Automatic restart after voltage failure
- 3.24 Activating password protection
- 3.25 Calling up/modifying protection settings
- 3.26 Test screens
- 3.27 Web server
- 3.28 Programmable settings
- 4 Elektronikon Graphic Controller
- 4.1 General
- 4.2 Control panel
- 4.3 Icons used
- 4.4 Main screen
- 4.5 Calling up menus
- 4.6 Shutdown warning
- 4.7 Shutdown
- 4.8 Inputs menu
- 4.9 Outputs menu
- 4.10 Counters
- 4.11 Control mode selection
- 4.12 Service menu
- 4.13 Setpoint menu
- 4.14 Event history menu
- 4.15 General settings menu
- 4.16 Info menu
- 4.17 Week timer menu
- 4.18 Test menu
- 4.19 User password menu
- 4.20 Web server
- 4.21 Programmable settings
- 5 Installation
- 6 Operation
- 7 Preventive maintenance
- 8 Adjustments and servicing procedures
- 9 Problem solving
- 10 Technical data
- 11 Instructions for use
- 12 Guidelines for inspection
- 13 Pressure equipment directives
- 14 Declaration of conformity
Compressors with built-in refrigeration dryer
Minimum
setting
Factory
setting
Maximum
setting
Starting pressure
Starting pressure (8 bar compressors) bar(e) 4 6.8 7.8
Starting pressure (8 bar compressors) psig 58 98.6 113.1
Starting pressure (10 bar compressors) bar(e) 4 8.8 9.8
Starting pressure (10 bar compressors) psig 58 127.6 142.1
Minimum
setting
Factory
setting
Maximum
setting
Stopping pressure
Stopping pressure (8 bar compressors) bar(e) 4 7.8 7.8
Stopping pressure (8 bar compressors) psig 58 113.1 113.1
Stopping pressure (10 bar compressors) bar(e) 4 9.8 9.8
Stopping pressure (10 bar compressors) psig 58 142.1 142.1
Parameters
Minimum
setting
Factory
setting
Maximum
setting
Allowed number of motor starts per day 72 720 720
Power recovery time (Automatic restart
function)
s 60 60 3600
Restart delay s 0 0 1200
Communication time-out s 10 30 60
Protections
Minimum
setting
Factory
setting
Maximum
setting
Ambient temperature warning level °C 0 40 40
Ambient temperature warning level °F 32 104 104
Ambient temperature shutdown level °C 0 45 45
Ambient temperature shutdown level °F 32 113 113
Service plan
The built-in service timers will give a Service warning message after their respective pre-programmed time
interval has elapsed.
Also see section Preventive maintenance schedule.
Consult Atlas Copco if a timer setting has to be changed. The intervals must not exceed the nominal
intervals and must coincide logically. See section Service menu.
Instruction book
2920 7110 21 111