Product Manual
Table Of Contents
- Table of contents
- 1 Safety precautions
- 2 General description
- 3 Elektronikon controller
- 3.1 General description
- 3.2 Control panel
- 3.3 Icons used on the display
- 3.4 Main screen
- 3.5 Shut-down warning
- 3.6 Shut-down
- 3.7 Service warning
- 3.8 Scrolling through all screens
- 3.9 Calling up element and dew point temperatures
- 3.10 Digital inputs
- 3.11 Calling up running hours
- 3.12 Calling up motor starts
- 3.13 Calling up module hours
- 3.14 Calling up/resetting the service timer
- 3.15 Selection between Local, Remote or LAN control
- 3.16 Calling up/modifying CAN address control
- 3.17 Calling up/modifying IP, Gateway and Subnetmask
- 3.18 Calling up/modifying pressure band settings
- 3.19 Modifying pressure band selection
- 3.20 Calling up/modifying service timer settings
- 3.21 Calling up/modifying unit of temperature
- 3.22 Calling up/modifying unit of pressure
- 3.23 Automatic restart after voltage failure
- 3.24 Activating password protection
- 3.25 Calling up/modifying protection settings
- 3.26 Test screens
- 3.27 Web server
- 3.28 Programmable settings
- 4 Elektronikon Graphic Controller
- 4.1 General
- 4.2 Control panel
- 4.3 Icons used
- 4.4 Main screen
- 4.5 Calling up menus
- 4.6 Shutdown warning
- 4.7 Shutdown
- 4.8 Inputs menu
- 4.9 Outputs menu
- 4.10 Counters
- 4.11 Control mode selection
- 4.12 Service menu
- 4.13 Setpoint menu
- 4.14 Event history menu
- 4.15 General settings menu
- 4.16 Info menu
- 4.17 Week timer menu
- 4.18 Test menu
- 4.19 User password menu
- 4.20 Web server
- 4.21 Programmable settings
- 5 Installation
- 6 Operation
- 7 Preventive maintenance
- 8 Adjustments and servicing procedures
- 9 Problem solving
- 10 Technical data
- 11 Instructions for use
- 12 Guidelines for inspection
- 13 Pressure equipment directives
- 14 Declaration of conformity
9 Problem solving
Before carrying out any maintenance or repair, perform following steps:
•
Stop the compressor and switch off the voltage.
• Open and lock the isolating switch to prevent an accidental start.
• Isolate the compressor by closing the outlet valve.
• Depressurize the system by opening the drain valve(s).
Compressor
Condition Fault Remedy
The compressor does
not start.
Pressure too high. Compressor will start again when the
pressure drops to the starting pressure.
Loose connection. Check all electrical connections.
Safety valve blows. Pressure too high Check settings and correct.
Safety valve opens too soon. Replace valve.
Compressor capacity
or pressure below
normal.
Air consumption exceeds capacity of
compressor.
Check equipment connected.
Choked air inlet filter. Remove and check filter. Replace if
necessary.
Safety valve leaking. Replace valve.
Compressor element out of order. Consult your supplier.
Compressor module
overheating or
compressor shutdown
on high air
temperature.
Insufficient compressor cooling. Improve ventilation of compressor room.
Clean compressor element fins and fan,
see Cleaning the compressor element.
Cooling fan out of order. Check and correct.
Condensate trap
continuously
discharging air an
water
Automatic drain out of order Have the drain checked. Replace as
necessary
Refrigerant dryer
For compressors with a built-in refrigerant dryer also:
Condition Fault Remedy
Dew point too high Air inlet temperature too high Check and correct; see section
Reference conditions and limitations
Fuses blown Check fuses and remedy the cause.
Shortage of refrigerant Have circuit repaired or recharged.
Refrigerant compressor does not run See below
Evaporator pressure is too high See below
Condenser pressure is too high See below
Instruction book
2920 7110 21 133