Product Manual
Table Of Contents
- Table of contents
- 1 Safety precautions
- 2 General description
- 3 Elektronikon controller
- 3.1 General description
- 3.2 Control panel
- 3.3 Icons used on the display
- 3.4 Main screen
- 3.5 Shut-down warning
- 3.6 Shut-down
- 3.7 Service warning
- 3.8 Scrolling through all screens
- 3.9 Calling up element and dew point temperatures
- 3.10 Digital inputs
- 3.11 Calling up running hours
- 3.12 Calling up motor starts
- 3.13 Calling up module hours
- 3.14 Calling up/resetting the service timer
- 3.15 Selection between Local, Remote or LAN control
- 3.16 Calling up/modifying CAN address control
- 3.17 Calling up/modifying IP, Gateway and Subnetmask
- 3.18 Calling up/modifying pressure band settings
- 3.19 Modifying pressure band selection
- 3.20 Calling up/modifying service timer settings
- 3.21 Calling up/modifying unit of temperature
- 3.22 Calling up/modifying unit of pressure
- 3.23 Automatic restart after voltage failure
- 3.24 Activating password protection
- 3.25 Calling up/modifying protection settings
- 3.26 Test screens
- 3.27 Web server
- 3.28 Programmable settings
- 4 Elektronikon Graphic Controller
- 4.1 General
- 4.2 Control panel
- 4.3 Icons used
- 4.4 Main screen
- 4.5 Calling up menus
- 4.6 Shutdown warning
- 4.7 Shutdown
- 4.8 Inputs menu
- 4.9 Outputs menu
- 4.10 Counters
- 4.11 Control mode selection
- 4.12 Service menu
- 4.13 Setpoint menu
- 4.14 Event history menu
- 4.15 General settings menu
- 4.16 Info menu
- 4.17 Week timer menu
- 4.18 Test menu
- 4.19 User password menu
- 4.20 Web server
- 4.21 Programmable settings
- 5 Installation
- 6 Operation
- 7 Preventive maintenance
- 8 Adjustments and servicing procedures
- 9 Problem solving
- 10 Technical data
- 11 Instructions for use
- 12 Guidelines for inspection
- 13 Pressure equipment directives
- 14 Declaration of conformity
Overview
Text on image
(1)
Overview
(3) Real Time (hours)
(2)
Running Hours
(4)
Reset
Example for service level (A):
The figures at the left are the programmed service intervals. For Service interval A, the programmed
number of running hours is 2500 hours (upper row) and the programmed number of real time hours is 8760
hours, which corresponds to one year (second row). This means that the controller will launch a service
warning when either 2500 running hours or 8760 real hours are reached, whichever comes first. Note that
the real time hours counter keeps counting, also when the controller is not powered.
A new algorithm is implemented for a better protection of the compressor elements. The running hours will
be recalculated depending on the ambient temperature. A compressor continuously running in an ambient
temperature between 30 °C (86 °F) and 35 °C (95 °F) is working in harder conditions than an element
running at 20 °C (68 °F). Therefore a service done earlier (a time reduction of 30 % is applied in this
temperature zone) will protect the element in a better way. In the zone between 35 °C (95 °F) and 40 °C
(104 °F), the time reduction is 60 %.
The figures within the bars are the number of hours to go till the next service intervention. In the example
above, the compressor was just started up, which means it still has 2500 running hours or 8305 hours to go
before the next Service intervention.
Service plans
A number of service operations are grouped (called Level A, Level B, etc...). Each level stands for a
number of service actions to be carried out at the time intervals programmed in the controller.
When a service plan interval is reached, a message will appear on the screen.
After carrying out the service actions related to the indicated levels, the timers must be reset.
From the Service menu above, select Service plan (3) and press Enter. Following screen appears:
Instruction book
84 2920 7110 21