Technical data

21
5.1.4 Under floor heating
For a good operation of the domestic hot water supply, there must be no
undesired circulation through the appliance caused by a second pump of the CH
circuit.
Connect under floor heating with an electric shut-off valve (two-way valve) to
prevent circulation through the appliance when there is no demand for central
heating.
A. Boiler
B. Pump
C. Thermostatic control valve
D. Spring-operated non-return valve
E. Electrical shut-off valve 230 V ~
F. Radiators
G. Room/clock thermostat
H. Maximum thermostat
5.2 Connecting the gas supply
1. Connect the gas pipe to the appliance using the gas valve supplied.
2. Check the boiler's data plate to ensure that the appliance has been set for
the correct gas supply. The boiler is supplied for Natural Gas (G20). A
propane (G31) gas conversion set is available and an appropriate sticker is
included (see §7.7).
3. The meter governor should deliver a dynamic pressure of 20mbar for natural
gas or 37mbar for propane.
4. To prevent the ingress of foreign matter and possible damage to the air/gas
ratio valve, the gas supply pipe must be checked for contaminants prior to
connection to the boiler. Install a gas filter if necessary.
5. On final connection of the gas supply to the boiler, the complete gas
installation, including the meter, must be tested for gas tightness and purged
as described in BS6891.