User's Manual

User manual Version 1.0
ABLELink
Serial-Ethernet Server
GW51W-MAXI
Copyright © 2003 Atop Technologies, Inc.
All rights reserved. Designed in Taiwan.
23 / 54
4.3 Configuration set by hyper terminal console utility
1. Power off GW51W-MAXI.
2. Set the MODE switch SW1 to OFFand SW2 to ON’.
3. Use a PC to connect to GW51W-MAXIs console with RS-232 cross over cable.
4. Power on GW51W-MAXI.
5. Open a hyper terminal program from your computer Start menu -> Programs -> Accessories ->
Communication -> hyper terminal, set COM1 parameters as follows.
- Baud rate : 9600bps
- Data bit: 8 bits
- Parity: None
- Stop bit: 1bit
- Flow control: None
NOTE:
At present time baud rate is fixed at 9600bps for console port communication, RS-232C parameters
of your computer COM port and GW51W-MAXI must be the same.
6. Once hyper terminal is connected, type in username and password then the following hyper terminal
window appears.
7. The following configuration operations are totally the same as those configure by telnet.
8. After finishing console settings, power off GW51W-MAXI, put SW1 and SW2 back to the previous
setting.