6.3 Connecting the Gas Supply
Gas Supply Requirements
ALL INSTALLATIONS MUST COMPLY WITH LOCAL CODE
ORINTHEABSENCEOFLOCALCODE,MUSTCOMPLYWITH
THE MOST RECENT EDITION OF THE NATIONAL FUEL GAS
CODEANSIZ223.1/NFPA54ORCAN-B149.
Shut-off Valve
A shut-off valve must be installed upstream of the
gas control valve. This allows for the disconnection of the
fireplace for servicing and maintenance. See Fig. 6.3.
The fireplace and gas control valve must be disconnected
from the gas supply piping during any pressure testing of
thesystemattestpressuresinexcessof1/2psig.Forpres-
sureslowerthan1/2psig,isolatethegassupplybyclosing
the manual shut-off valve.
Control Valve Connection
The gas supply line connection to the elbow above
the shut-off valve is made through the inlet in the left
side of the fireplace. The gas supply line should be a
minimum3/8”insidediameter,ortheappropriatesizeto
provide sufficient gas pressure to the valve regardless of
the input setting.
The use of flexible gas appliance connectors is accept-
ableinmanyareasintheU.S.InCanada,methodsvary
depending on local code. If local codes permit, use flex-
ible gas line for ease of installation and service. For those
locales where flexible gas lines are not permitted, use a
3/8”ironfitting.
Securealljointstightlyusingappropriatetoolsand
sealing compounds (for propane units, be sure to use
compounds that are propane resistant). Turn on gas
supply and test for gas leaks using a leak test solution or
electronic gas sensor.
A T-HANDLE GAS SHUT-OFF VALVE IS
REQUIREDTOBEINSTALLEDINTHECOMMON-
WEALTH OF MASSACHUSETTS IN COMPLIANCE
WITH CODE 248CMR.
THISPRODUCTMUSTBEINSTALLEDBYA
LICENSEDMASTERORJOURNEYMANPLUMBER
OR GAS-FITTER WHEN INSTALLED IN THE
COMMONWEALTH OF MASSACHUSETTS.
Figure 6.3.
Typical gas supply fittings.
Liquid Leak Test
• UsealeaktestsolutionavailablefromanyHVAC
supplier. Do not use soap solutions as they may
containcausticchemicalswhichthemselvescan
cause leaks.
• Lightappliance-seelightinginstructionsonthe
back cover of this manual or on the rating plate.
• Brushorsprayalljointsandconnectionswiththe
test solution.
• Ifbubblesappearatanyconnectionorseamora
gas odor is detected, immediately turn gas control
knob to the OFF position.
• Tightenorreconnecttheleakingjointandretest
for any gas leaks.
NEVER USE AN OPEN FLAME TO CHECK FOR GAS
LEAKS.
ALWAYS REFER TO THE LIGHTING INSTRUCTIONS ON
THEINSIDEBACKCOVEROFTHISMANUALWHEN
LIGHTING THE FIREPLACE.