The line must be disconnected from the gas sup-
ply line by closing the main supply manual gas shut-
off valve (gas cock) during any pressure testing of the
gas supply piping system that is equal to or exceeds
pressuresof1/2psig(3.5kPa).
6.4TestingGasPressure
Proper gas pressure provides a consistent flow of
gas to the appliance and is instrumental in checking
for gas leaks. There are two pressure test points on
the front of the fireplace control valve where test
gaugeconnectionsaremade.SeeFig.6.4.Gauge
connections are identified by:
• Eforinletorsupplypressure(theamountofgas
coming to the valve.)
• Aformanifoldpressure(theamountofgasthatis
coming out of the valve to the burner.)
WARNING
DO NOT ALLOW THE INLET GAS PRESSURE TO
EXCEED 14.0WC(OR1/2PSIG)ASSERIOUS
DAMAGE TO THE VALVE MAY RESULT.
Inlet Pressure
MIN MAX
NaturalGas:5.0WC(1.24kPa)7.0WC(1.74kPa)
Propane:11.0WC(2.74kPa)13.0WC(3.24kPa)
Manifold Pressure
MIN MAX
NaturalGas:1.6WC(0.40kPa)3.5WC(.87kPa)
Propane:6.4WC(1.60kPa)10.0WC(2.48kPa)
ALWAYSTESTINLETPRESSUREWITHTHEVALVE
REGULATORCONTROLATTHEHIGHESTSETTING.
Symptoms of incorrect gas pressure include:
Insufficient gas pressure:
• Smallpilotflamewhichcanresultininsufficientmil-
livolts.
• LittlevariationinflamepicturebetweenHIandLO
regulator settings.
• Insufficientgastosupportmorethanoneappliance
causing nuisance outages or gas surges.
Excessive gas pressure:
• Permanentdamagetovalvecausingcompleteappli-
ance shut down.
• Toolargeapilotflameexcessivefuelconsumptionin
standingpilotmode(CPI).
• Sootingduetoimpingementand/orincorrectfuelto
air mix.
A - Manifold
E - Inlet
PilotAdjustment
Figure 6.4. Pressure test points located on the front of the valve.
Tools required:
• 1/2”openendedwrenchordeep-wellsocket,TorxT20
orslottedscrewdriver,7/16”open-endwrench.
Conversion Kit Contents:
• 4mmhexkey
• 1,regulatortowerlabeledforeitherLPorNG
• 2,regulatortowerscrews
• 1,burnerorifice(#40forNG,1.55forLP)
• 1,pilotorifice(#62-NG/#35-LP)
• LabelA-tobecompletedandappliedto
the back of the stove
• LabelB-applytothestove’sRatingPlate
• Smallvalvelabel-applytovalvebody
• 1,#8X1/2”sheetmetalscrew(LPAirShutterLock)
6.5 Fuel Conversion
TheGZ455DVisshippedfromthefactoryequippedto
burnNATURALGASonly.IfPROPANEgasistobeused
as fuel, the appliance must first be converted for using
PropaneConversionKit157409includedwiththestove.
UseNGConversionKit157408tochangebackforusewith
natural gas.
WARNING:
THECONVERSIONKITISTOBEINSTALLEDBYAN
AUTHORIZED JØTUL SERVICE TECHNICIAN IN ACCOR-
DANCE WITH THE MANUFACTURER’S INSTRUCTION
AND ALL CODES AND REQUIREMENTS OF THE AU-
THORITY HAVING JURISDICTION. FAILURE TO FOLLOW
THESE INSTRUCTIONS COULD RESULT IN SERIOUS IN-
JURY OR PROPERTY DAMAGE. THE QUALIFIED AGENCY
PERFORMINGTHISWORKASSUMESRESPONSIBILITY
FOR THIS CONVERSION.
IN CANADA:
THECONVERSIONSHALLBECARRIEDOUTINACCOR-
DANCE WITH THE REQUIREMENTS OF THE PROVINCIAL
AUTHORITIES HAVING JURISDICTION AND IN ACCOR-
DANCEWITHTHEREQUIREMENTSOFTHECAN1-B149.1
AND .2 INSTALLATION CODE.