Specifications

Purchase order no. 7/EDP/COMP/106 Dated : 30/09/2011
10
S.
No.
DESCRIPTION
Quantity
UNIT
PRICE
inclusive
of Excise,
Custom
Duty,
Freight &
Forwardin
g,Insuran
ce,
Installatio
n &
Commissi
oing
Charges
CST /
ST (In
Figure)
Service
Tax (In
Figure)
Total Unit
Price F.O.R
Destination
incl. of
CST/ST,
Service Tax,
,Freight
&Forwardin
g, Custom
Duty,
Insurance,
Installation
&
Commissioi
ng Charges
etc.
Total
Amount
F.O.R
Destination
incl. of
CST/ST,
Service
Tax, Freight
&Forwardin
g, Custom
Duty,
Insurance,
Installation
&
Commissioi
ng Charges
etc.
All figures in Rs.
1 2 3 4 5 6 7 8=7*3
1.8
Server for Talwara, Sundernagar & Nangal
with the same Config as at 1.7 but with
3 177400 8870 0 186270 558810
CPU 1 x Intel Xeon Quad Core
Processor E5620 (2.4 GHz or
higher with 12MB Cache or
higher & 5.86 GT/s or higher )
or Higher
Memory 12 GB Registered DDR3 with
ECC, 1066 MHz or higher
Memory upgradable to 192 GB
through 12 DDR3 DIMMs
Monitor 19" LCD Monitor, TCO'05
Certified, Make same as that of
Server
2
SYSTEM SOFTWARE
2.1 WINDOWS 2008 ENTERPRISE SERVER 64 Bit
Edition OLP WITH MEDIA ( Incl Client Access
License for 10 users)
9 103130 5156.5 10622 118909 1070178
2.2 EXCHANGE SERVER 2010 ENTERPRISE OLP
WITH MEDIA AND FOREFRONT THREAT
MANAGEMENT GATEWAY 2010 with MEDIA
Version
1 389328 19466 40101 448895 448895
2.3 EXCHANGE SERVER 2010 STANDARD OLP
WITH MEDIA or Latest Version
2 28814.3 1440.7 2968 33222.8 66446
3
POWER CONDITIONING EQUIPMENT
3.1
ON LINE UPS OF 5 KVA RATING
4 41000 2050 0 43050 172200
Power Rating
5KVA
Technology DOUBLE CONVERSION On-
line UPS using IGBT & having
Isolation Transformer for total
isolation from mains.
INPUT
Nominal
Voltage Range
230 V - 25 % + 10% , Single
Phase
Nominal
frequency
Range
50 Hz ± 5%
Power Factor
Not less than 0.95
Wave Form
Sinusoidal
OUTPUT
Continuous
output Power
5 KVA/ 3.5 KW or higher
Voltage
230 V, Single Phase
Voltage
Regulation
Not more than 2%
Frequency
50 Hz ± 0.5 Hz
Overload
Capacity
110% for 10 minutes and 150%
for 10 seconds120% for 30
secs
Wave Form
Sinusoidal
Load Power
Factor
0.7 to 0.8
COMPUTER & COMMUNICATION INTERFACE
Should be available & the software should be
capable of monitoring UPS activity & to ensure
orderly shutdown of the server in case of battery
low voltage/discharged condition. Software
required for Windows Server 2008. SNMP Based
real time monitoring of all vital parameters such as
Input voltage, Output Voltage, Output Load,
Battery Voltage om Windows.
MEASURING INSTRUMENTS (ANALOG OR
DIGITAL)