Instruction manual
14 
thermostat.  In case the temperature in the boiler does not exceed  65 °C in 2 hours of burning up 
time, the regulator stops the flue gas ventilator and switches on the control light - fuel shortage. 
In the time of burning out the boiler when the temperature falls under 65 °C and this condition lasts 
for more than 30 minutes, the regulator stops the flue-gas  fan and the control light of fuel shortage 
shines on. 
Fuel shortage 
When the temperature of heating water in the boiler falls under  65 °C and this condition lasts for 
more than 30 minutes, the regulator  stops the flue-gas fan and the control light of fuel shortage 
shines on. If in the burning up process the boiler temperature does not raise to more than  65°C, 
fuel shortage will be shining on the display for more than 2 hours. To start the regulation again, it is 
necessary to: 
- refuel the boiler; 
- burn the boiler up 
- turn the turning button of the boiler thermostat into the  maximum  left position and thus stop the 
alarm; 
-wait until the control light of fuel shortage flickers; 
- by turning button of the boiler thermostat set up the required temperature of the boiler and the 
regulator starts the process of burning up 