Instruction manual
16 
Technical description of the ATTACK DPX LAMBDA:  
Combustion regulation 
The boiler output is regulated by means of the exhaust temperature – to the O2 value and by means 
of air flaps - actuators for the primary air and secondary air. The burn-off occurs with the adjusted 
exhaust    temperature  set  value.  If  the  boiler  temperature  increases  to  90°C  (Over  temperature) 
because there is too much fuel (buffer is fully loaded), the exhaust fan is switched off, the primary 
air flap is closed and the secondary air flap is opened on 25%. If the boiler temperature decreases to 
to less  than  88.5°C,  the  secondary air  flap  is  opened  for  30sec  on  100%  (chimney  cleaning), 
afterwards the primary air flap is regulated following exhaust temperature requirement. 
The  automatic  switch  off  of  the  boiler:  Switching  off  the  boiler  after  the  fuel  is  used,  can  be 
alternatively done by means of exhaust temperature (TAG) or by the O2 value (function adjustable). 
Switch  off  by  exhaust  gas  temperature  adjustment:  If  the  fuel  is  used  and  the  exhaust  gas 
temperature decreases for less than 25% of the nominal exhaust temperature, the boiler is switched 
off after 15 minutes. This is recommended only with very big woodlogs or with very humid fuel. 
Switch off by Oxygene: If the boiler runs for longer than 45 minutes and the O2 value rises for 15 
minutes over 14%, the boiler is switched off. This should be the standard function, because cooling 
down of the boiler by the  chimney is limited.  The remaining rest  of  coal makes  easier  renewed 
firing and proves the lowest issues while heating-up. 
After  boiler  switch  off,  the  exhaust  fan  is  switched  off,  the  primary  air  flap  is  closed  and  the 
secondary air flap still remains on 25% open until the exhaust temperature sinks under 100°C. 
After switching off the boiler (automatically or manually): The primary air flap V1 is closed (0%), 
the exhaust temperature  is >100°C, the secondary air  flap  (V2) stays open to min.  25%  and  the 
automatic operation continuation remains deactivated. 
Heating-up and refuelling: 
Basically: Before heating up, pay attention to heating system pressure (water level)! 
Fuel has to be ready in the boiler! 
Ignit the fuel (use operation prescriptions of the boiler) 
Check requirement for warmth and external temperature, as well as  the residual supply in 
the hopper 
Heating-up or refuelling only: 
  If it is possible due to the requirement for warmth and residual supply in the hopper, check 
thermometers in the hopper. 
Right firing-up follow (see operating instructions to the boiler)! 
Effect: Maximum exploitation of the fuel. 
Introduction: Make up the fire first, when the boiler is switched off (control light 1 does not shine),  
Additional fuelling in “Boiler ON” status 
The fuel has to be loaded immediately and the filling door must be immediately closed!  