Temperature reaches 299°C and less, the exhaust fan is switched on again. This is protection against 
exhaust fan and/or the exhaust sensor damage. 
Boiler overheating
If the buffer is completely filled because too much fuel was loaded, the boiler temperature increases 
to  more  than  90°C. Overheating  occures  and the  exhaust  fan is  automatically  switched  off.  The 
display flashes and the text display appears: 
Over temp. 
DO NOT OPEN! 
Boiler  door(s)  may  not  be opened!  Overheating  brings high  consumption  of  fuel  and  ecological 
damages. 
Operating mode display while the boiler is switched off 
If the fuel is used, the controller switches off the boiler automatically; however, the boiler also can 
be switched off manually with the “+”  button (this serves only for the security disconnection, e.g.: 
no water in the boiler). Directly after switching off, the text display occures: 
After 15 min. becomes the lighting of the text display) switched off. 
Operating mode display while the boiler is switched off 
If the fuel is consumed, the controller switches off the boiler automatically; however, the boiler also 
can by hand with the button “-” switched off (this serves only for security disconnection, e.g.: when 
there is no water in the boiler). Directly after switching off, the text display occures: 
BOILER TEMPERATURE 
°C 
After 15 min. is illumination of the text display switched off. 
Automatic protection functions 
If the boiler is not heated within 7 days, the exhaust fan is switched on for 2 min. and the boiler is 
“rinsed” with fresh air to keep it dry. At the same time, the return valve and loading valve work and 
the loading pump is switched on for 10 seconds. During this process the text display indicates: 
PROTECTION FUNCTION 
PLEASE WAIT 
After finishing the protection functions, display is automatically switched to the operating mode. 
Information about current operation staten about toperating state . 
The menu button“←”allows entrance into menu “Selection” in which different submenus can be 
selected and the first submenu “Information” appears immediately. With the menu button “←” you 
enter into submenu “Information” where you can get different information with buttons “+” and “-”. 
To exit from the menu use “ ←” button; after exit it is automatically switched to operation display. 
If no button is pressed for 30 min., it is automatically switched to operation display. 
If  error  or  excessive  temperature appears,  the  menu will be  left  automatically.  Display  shows 
following information: 