Settings for the commission of the ATTACK DPX LAMBDA . 
The start-up of device is enabled,  when the minimum requirements for test- or heating operation 
are fulfilled (see chapter 1.2). Afterwards it is necessary to carry out the following settings. 
Settings with usage of the service technician´ s code 
The  menu  button  „
←“enables entrance  into  menu  “Selection”, where  it  is  possible  to  select  the 
„Settings“ submenu by buttons “+” or “-”. The choice of “Settings” is confirmed with the button “ 
„←”. 
The exit from the submenu automatically occurs after setting  of the "connection valve" with the 
menu button “ ←”; after exit it is automatically switched to the operating display. 
If no button is pressed for 1 min., it is automatically switched to the operation display. 
Settings: 
Menu  Submenu  Indication 
Information 
Test of device 
Safety test 
Code insert 
 --- 
Set the code by „+“ button. Random 
number lights on the left side. Insert code 
and confirm by „←“ button. Technician´s 
number is available from supplier of the 
boiler.  
01 :Language 
German DE 
English GB 
Italian IT 
French FR 
Swedish SE 
Polish PL 
Slovak SK 
Czech CZ 
Dutch NL 
Danish DK 
Hungarian HU 
Slovenian SI 
Function: Setting of national language 
02 : Setting of boiler 
°C 85 
Function: Set boiler temperature 
Producer: 85°C 
Range of setting: 75°C – 85°C 
03 : Setting of TAG 
°C 180 
Function: After setting of flue gas 
temperature (nominal 180°C boiler output). 
Producer: 180°C 
Range of setting: 110°C up to 240°C 
Tip: TAG = flue gas temperature 
04 : Setting of O
2 
% 6,0 
Function: Setting of O
2
 value for 
combustion 6 % 
Producer 6,0 % 
Range of setting: 4,0 % up to 8,0 % 
Setting 
05 : Start TAD 
K 60 
Function: to reach sufficient output before 
the feeding door is closed 
Producer: 60K 
Range of setting: 25K up to125K 
Tip: TAD= temperature difference. It is 