space of min. 1meter. This space is necessary for basic operation, maintenance and service of the 
boiler. Location of the boiler in the dwelling spaces (including halls) is not allowed! The   cross 
section  of  opening  for    air  inlet    to  the  boiler  room    is  recommended  to  be  at  least  200  cm², 
depending on the boiler output. 
ATTENTION!  
The objects from easily combustible materials cannot be placed on the boiler or the nereby 
in the distance shorter than the safe distance. 
If there is a danger of  fire or blow up during the work  (e.g. the work with texture materials, sizing 
materials, etc.) the boiler must be out off operation. 
Air inlet 
For correct boiler operation, it is necessary to provide sufficient air inlet for combustion. Minimum 
cross section of the opening for fersh air inlet is 200 cm². 
Connection of boiler to the heating system 
Only trained service technician is allowed to install the ATTACK DPX boiler and to do the service 
actions. Before boiler installation into older heating system, it is necessary to wash (to clean) the 
whole system. Heating system has to be filled with water, conforming to requirements of the STN 
07 7401:1991, particularly its callosity cannot exceed 1mmol/l and concentration of Ca2+ must not 
exceed 0,3 m mol/l. 
In case that these conditions will not be kept, the boiler warranty expires! 
Chimney 
Connection of the appliance to the flue must be always done with approval of authorized chimney-
sweeping  company. There must always be sufficient draft in the flue and flue gas must be draught 
to the atmosphere in all possible operation conditions. For the correct operation of the boiler, the 
independent flue must be dimensioned in the right way, because combustion, output and service life 
of boiler depends on the   draught.  The draught is influenced by the section  of flue, height and 
roughness of the internal wall. Into the flue where the boiler is attached, no other appliance can be 
attached. The flue diameter must not be smaller than the outlet on the boiler. Flue draught must 
have the specified values. But it must not be too high so as not to decrease the efficiency of boiler 
and  interrupt  burning.  If  the  draught  is  too  strong,  install  a  throttle  valve  between  the  flue  and 
boiler. 
Information values of the chimney´s cross section: 
20 x 20cm     min. height 7m 
O 20cm     min. height 8m 
15 x 15cm     min. height 11m 
O 16cm     min. height 12m 
Exact chimney dimension is stated by the STN 73 42 10. Prescribed chimney draught is given in the 
Technical parameters. 
Exhaust pipe 
Exhaust pipe must have the outlet into the chimney. If the boiler cannot be attached to the chimney 
directly,  the  exhaust  pipe  must  be  as  short  as  possible  and  not  longer  than  1m  without  heating 
surface and it must rise in direction to the flue. Exhaust pipes must be tight and resistant against flue 
gas leakage and cleanable from inside. Exhaust pipes must not lead through other´s dwelling and 
utility premises and the internal section of the exhaust pipe  must not taper in direction to the flue. 
Usage of bents is not suitable. 