Instruction manual
33 
Connection with heat accumulators 
Connection system is based on principle of heating up of water in accumulation tanks, where the 
warmth is gradually taken away from the tanks according to the request from the heating system. 
By the operation with several heating ups at full performance, accumulation tanks will be 
heated for the temperature of 90-100°C. Heating with accumulation tanks in connection with the 
ATTACK DPX boiler brings more advantages. To the main advantages belongs longer boiler life-
time and also lower consumption of fuel. Recommended volumes of accumulation tanks according 
to boiler output are following: 
DPX25 - 1500 - 2000 l 
DPX35 - 2000 - 2500 l 
DPX45 - 2500 - 3000 l 
Operation with accumulation tanks 
After heat-up phase, the boiler heats the water in the accumulation tank to 90 - 100°C by full output 
in 1-3 feedings. After burn-out, the heat is taken through the three-way valve only from the 
accumulation tank. The  offtake  period  depends  on  the  tank  volume and  external temperature.  In 
heating season it can be 1 - 3 days (if the prescribed min. volume is respected). If it is not possible 
to use the prescribed volume of the tank, it is recommended to use at least one tank of 500l volume 
for start and finish boiler operation. Minimum volume of accumulation tank is given in the tabel 
of technical parameters. 
Standardly delivered accumulation tanks 
Type of tank  Volume (l)  Diameter (mm)
Height (mm)  Heat-exchange surface 
(m2) 
AK 500  500  650  1650   
AK800  800  790  1730   
AK1000  1000  790  2050   
AS500  500  650  1650  2,0 
AS800  800  790  1730  2,4 
AS1000  1000  790  2050  2,8 
Tank isolation 
Accumulation tanks ATTACK AK500, AK800, AK1000, AS500, AS800 and AS1000 are delivered 
with detachable isolation of soft polyurethane with red leatherette surface.