Possible faults and methods of their deletion 
Fault  Cause  Solution 
Control light „Net“ does 
not lighti  
No voltage in mains 
Incorrectly plugged craddle into 
socket 
Faulty network switch 
Broken inlet conductor 
Check 
Check 
Replace 
Replace 
Boiler does not reach 
required parameters  
Water shortage in the system 
High pump output 
Boiler output is not sufficiently 
dimmensioned for concrete system 
Low quality wood 
Heat-up flap does not seal 
Low chimney draught 
Long heating-up or operation with 
opened heat-up flap 
Deformed fan wings 
Unsufficiently cleaned boiler 
Blocked air inlet into combustion 
chamber. 
Refill 
Set overflow and switching 
Matter of project 
Combust dry and cut wood 
Repair 
New chimney, unsuitable 
connection 
Put throttle into flue gas 
connection 
Close heat-up flap 
Replace 
Clean 
Clean 
Door do not seal   Damaged glass cord 
Jet gets blocked 
Low chimney draught 
Replace, adjust door hinges 
Do not burn small wood pieces 
and wood crust 
Faulty chimney 
Fan has no rotations or it 
is noisy  
When using irreversible safety 
thermostat, it comes to overheating 
Blocked radial impeller 
Faulty condensator 
Faulty motor 
Faulty contact in the socket of 
motor inlet conductor 
Push reset button 
Clean the fan 
Replace 
Replace 
Check 