Errors and warnings with the ATTACK DPX LAMBDA system  
By following errors and warnings it is not possible to burn in the boiler: 
- red display 3 lights (error), operation of the wood boiler is not possible 
- red display 3 flickers (warning), correct operation of the wood boiler is not possible. This text 
automatically expires after the cause is removed. 
Boiler operation is possible by emergency programm, if: 
- yellow display 2 (warning) lights 
All emergency programs in the regulator menu are automatically expalined and serve for the short-
time keeping of the heating operation. Thereby: 
Immediate error removal is recommended!! 
Too long operation by appropriate emergency program may cause chimney and boiler damage - the 
warranty is not valid. 
Emergency thermostat is switched on (error) 
Cause:  
Temperature in the boiler >95°C is caused by 
fuel surplus, power shortage, fault at warmth 
offtake (or in circuiting pump) 
Control light 3 red  lights 
Correction:  
Use less fuel! Check warmth offtake! 
Reset: 
Screw out the cover (8) and press STB button 
placed underneath, when the text „boiler 
temperature 85°C appears“! Error is 
automatically removed within few seconds. 
Emergency program:  
Actions of regulator: 
No 
Automatic boiler stop. 
Boiler temperature > 86°C, offtake of residual 
warmth is switched off 
V1 and V2 are adjusted after setting 
STB on 
reset 
Boiler temperature 
(°C) 
If the error repeats, it is necessary to inform the service technician. 
Incorrectly measured values of boiler temperature (error)
Cause: 
Control light 3 red 
Measured values < -20°C, or > +150°C 
Lights 
Correction:  
Reset: 
Check sockets and conductors! Replace 
sensors, if necessary! 
Automatically after removing the cause 
Error in measuring 
of boiler temperature 
Boiler temperature 
(°C) 
Emergency program:  
Actions of regulator: 
No 
Automatic stop of flue gas fan and circuiting 
pump 
V1=0 %, V2= min. 25 % open 