Instruction manual
39 
Antifreeze protection (warning) 
Cause: 
Control light 2 yellow: 
Correction: 
Reset: 
Boiler temperature is < 7°C, when the boiler 
is switched off 
Lights 
Do heat-up and burn-out 
Automatically with new burn-out (button +), 
or when the boiler temperature is > 8°C 
Emergency program:  Yes, burn-out is possible - do that! 
Antifreeze protection 
Boiler temperature 
(°C) 
Actions of regulator:  At boiler temperature < 7°C: 
Circuiting pump starts 
By this action, if there is warmth of the tank, 
it is taken off. If there is no warmth in the 
tank, the freezing point in circuiting water 
decreases. 
At boiler temperature > 8°C: 
Circuiting pump is switched off 
Incorrectly measured values of Oxygene sensor – Lambda probe (error) 
Cause: 
Control light 2 yellow 
Non-apparent heating by means of sensor 
error in electric circuit or short circuit 
Lights 
Correction: 
Check sockets and conductors. 
Demount and clean oxygene sensor. If it is 
necessary, replace it. 
Reset: 
Emergency program: 
Actions of regulator: 
Automatically after error removing and 
resetting of scale of the oxygene sensor. 
Regulator works with alternative air V1 and 
V2. After burning-out, the boiler must be 
manually switched off by the „-“ button. 
Error in measuring 
O2 
Boiler temperature 
(°C) 
Not to shorten the boiler´s life-time, it is necessary to remove the 
error immediately! Possible expiration of warranty! 
Errors, functions and actions of regulator - summary 
Errors and functions   Actions or operation of the regulator  
Power failure  When the power is supplied again, the operation state is 
regenerated, same as it was before.(boiler starts or stops again) 
Too high boiler temperature  < 90°C: fan is stopped 
> 89°C: fan is switched on 
Incorrectly measured values 
of boiler temperature 
Stop of flue gas fan and connection pump. It is not possible to 
turn the boiler on. 
Incorrectly measured values 
of flue gas 
It is possible to turn the boiler on. Regulator works with 
alternative air V1 and V2. After burning-out, the boiler must 
be switched manually! 
Incorrectly measured values 
of O2 sensor (Lambda probe) 
While heating-up, no line graph is dislayed.It is possible to 
turn the boiler on, regulator works with spare air V1 and V2. 
Automatic function of switch  If the boiler is switched on for 30 minutes and flue gas 










