Instruction manual
40 
off by the flue gas sensor  temperature decreases for 25% within 15 minutes, the boiler is 
switched off. 
The STB is started  Residual warmth off-take is stopped, if the boiler temperature 
is < 85°C. If, then, the boiler temperature increases to > 86°C, 
usage of residual warmth starts again. 
Function of switching contact  When the boiler is switched on: WK/AK is closed 
When the boiler is switched off and flue gas temperature is 
<100°C: WK/RK is closed 
Error of CPU  All relays are turned off by Hardware Watchdog 
Antifreeze protection  When the boiler is switched off and the temperature is < 7°C: 
Start of connecting pump, Y1 a Y2 = 100%. 
If boiler temperature increases to > 8°C, connecting pump is 
stopped. 
Y1=0%, Y2= 100%. 
Protection of flue gas fan and 
of flue gas sensor against 
overheating 
Flue gas temperature > 350°C, flue gas fan is stopped 
Flue gas temperature < 299°C, flue gas fan is switched on 
Short circuit of the „+“ button  Button of regulator does not react, even not to significant 
pressure 
Enter function (Menu)  After safety time, the menu automatically expires 
Safety test  It takes max. 30 min and finishes automatically or it is aborted, 
if: boiler temperature is > 110°C or the „+“ button was not 
pressed for 30 seconds 
Operation range of automatic 
setting of C.H. return 
connection to determined 
value 
Between 60°C and 80°C 
Operation without settings 
controlled by technician 
Regulator is adjusted after setting by producer 
Data storaging  Only by sufficient energy > 160V. 










