Instruction manual
8 
Instrument panel  
ATTACK DPX STANDARD  
The wood gasifying boiler "ATTACK DPX Standard" is controled by boiler and flue gas 
thermostat. 
1 – Emergency 
thermostat with reset 
2 - Fuse 
3 - Main switch 
4 - Flue gas thermostat 
5 - Boiler thermostat 
6 –Thermomanometer 
Description: 
1.  Emergency thermostat with reset - boiler protection against overheating (after reaching 
temperature higher than 110°C it comes to boiler disconnection from electricity mains) after 
decrease of water temperature under 85°C it is necessary to push the restart button manually 
after removing cover of reset . 
2.  Fuse - boiler protection against short circuit 
3.  Main switch - boiler start and complete boiler stop for the case of need. 
4.  Flue gas thermostat - at decrease of flue gas temperature under adjusted value is the fan 
switched off 
ATTENTION! While heating-up, set this thermostat to 0°C. After fuel burn-out set the flue 
gas thermostat to „Operation“. When the temperature decreases under adjusted value, the 
suction fan is switched off. If you wish to turn the fan on again, set the lower temperature on 
the flue gas thermostat. It is necessary to test the optimum setting for operation. 
5.  Boiler thermostat - serves for setting of max. temperature of water in boiler (after exceeding 
of adjusted value is the fan switched off and boiler works at minimum output, after decrease of 
given temperature is the fan switched on again and boiler works at maximum output). 
6.  Thermomanometer - indicates outlet water temperature from the boiler and operation pressure. 
Pull rod of the chimney flap - serves to open and close the heat-up flap (everytime the feeding door 
is opened). 
Lever for exchanger cleaning - serves for cleaning of exchanger´s tubes 