Setup guide

Chapter 4
Rack Mounting the
Avid Nitris DNA Enclosure
This section provides the information for mounting the Avid Nitris DNA in a
19-inch (483-mm) National Electrical Manufacturers Association (NEMA) or
Electronics Industries Association (EIA) rack. Avid recommends that you
mount your Avid Nitris DNA in a rack before you connect any cables.
n
If you need to rack mount the HP workstation, a rack-mount kit is available
from HP. Installation instructions are included with the kit. The
HP Workstation system requires 5 rack units.
This section contains the following sections:
Equipment Environmental and Safety Guidelines
Installing the Avid Nitris DNA in a Rack
Equipment Environmental and Safety Guidelines
When you install the Avid Nitris DNA in a rack, you must take the following
precautions:
Elevated Operating Ambient Temperature — When the
Avid Nitris DNA is installed in a closed or multiunit rack assembly, the
operating ambient temperature of the rack environment might be greater
than the room ambient temperature. Therefore, consider installing the
equipment compatible with the manufacturer’s maximum ambient
temperature of 104°F (40°C).
Reduced Airflow — Do not compromise the amount of airflow required
for safe operation of the equipment.