Installation manual
For more information call your Leviton representative or the Leviton Technical Hotline at 800-722-2082
© Copyright 2001 Leviton Manufacturing Co., Inc.
8-5
2. Punch out one or both of the cable entry knockouts
that are also located at the bottom of the module
housing and pull your cable(s) through
3. Secure your electrical cable with a standard conduit
fitting or cable clamp (not included)
4. Drop the housing into its opening
Next, connect the incoming power cable to the surge
suppressor receptacles. the wiring connections will
depend on whether one or two dedicated circuits are
being run to the AC Power Module. The diagram on the
previous page shows the installation of the receptacles
using the single cable of one dedicated circuit:
1. Attach a “pigtail” or short piece of white NEUTRAL
(N) conductor to the SILVER terminal screws on each
receptacle. These screws are located on the sec-
tions labeled WHITE on the back of the receptacles.
2. Twist the two white pigtails together with the white or
NEUTRAL conductor from the incoming power
cable, securing the ends with an appropriate wire
connector.
3. Attach a black or HOT pigtail to each BRASS colored
terminal screw on the back of each receptacle.
These screws are located on the sections labeled
BLACK on the back of the receptacles.
4.Twist the two black pigtails together with the black
(HOT) conductor from the incoming power cable,
securing the ends with an appropriate wire connec
tor.
5. Twist the GREEN ground leads from the recepta-
cles with the GREEN or BARE copper grounding
conductor from the incoming power cable, securing
the ends of the wires with an appropriate wire con-
nector.
6. Carefully place the receptacles into the housing,
being sure that all wiring is safely tucked inside the
housing.
7. Secure the AC Power Module to the SMC using the
four #6 X 3/8” screws that come with the module,
tightening the module securely; these screws also
secure the module’s housing to the SMC.
8. Test the module by turning the power to its dedicat-
ed circuit(s) on at the service panel.
9. Until the work is completed, install safety plugs into
the receptacles to protect them from construction
debris.
If you’re installing two separate dedicated circuits, each
incoming cable will connect directly to a single recepta-
cle without the use of pigtails or wire connectors.
8
PRE-WIRE
Installation,
Labeling and
Documentation
Pre-Wire
Installation