User manual

Nr. Sound Tone frequency
DIP-switch
2nd stage
alarm (Hz)
L
M H
L
M H
1 LF Sweep 800 - 1000Hz @ 0.5 sec 1 1 1 1 1 800 cont 7 12 18 86 101 106
2 Alternative warble BS standard 800/960Hz @ 2Hz 1 1 1 1 0 800 cont 7 12 17 86 100 105
3 Warble Tone BS standard 800/1000Hz @ 0.5 sec 1 1 1 0 1 800 cont 7 12 18 87 101 106
4 Alternative warble BS standard 500/600Hz @ 2Hz 1 1 1 0 0 500 cont 6 10 13 84 99 102
5 HF Back up interrupted tone 2800Hz @ 1.0 sec on/off 1 1 0 1 1 2800 cont 8 17 35 93 106 114
6 LF Back up Alarm 800Hz @ 150 msec on/off 1 1 0 1 0 800 cont 6 9 12 80 95 99
7 HF Back up interrupted tone - fast 2800Hz @ 150 msec on/off 1 1 0 0 1 800 cont 7 16 35 92 105 113
8 LF Continuous tone BS5839 800Hz cont 1 1 0 0 0 Same tone 7 11 16 82 96 100
9 Sweep tone ( 1Hz) 800/900Hz @ 1Hz 1 0 1 1 1 800 cont 7 12 19 87 101 106
500-1200
3.75 sec on
0.25 sec off
500-1200
3.5 sec on
0.5 sec off
12 Analogue sweep tone 500/600Hz @ 2Hz 1 0 1 0 0 500 cont 6 10 13 84 99 102
13 Sweep tone (3Hz) 800/970Hz @ 3Hz 1 0 0 1 1 800 cont 7 12 17 85 100 105
14 Alternate HF slow sweep 2350/2900Hz @ 3Hz 1 0 0 1 0 2400 cont 8 16 32 92 106 113
15 Fast HF sweep 2400-2800Hz @ 7Hz 1 0 0 0 1 2400 cont 8 16 32 92 105 112
950Hz for 0.5 sec on 0.5 sec offx3
then 1.5 sec then repeat
17 Interrupted tone BS standard Interrupted tne 800Hz @ 0.5 sec on/off 0 1 1 1 1 800 cont 6 9 12 81 96 100
18 ISO 8201 LF BS5839 Pt 1 1988 Intermittent 970Hz 500ms on/500ms off 0 1 1 1 0 Same tone 6 11 13 87 101 106
19 Interrupted tone medium 1000Hz @ 0.25 sec on/off 0 1 1 0 1 800 cont 6 9 12 86 101 105
20 ISO8201 HF Intermittent 970Hz 500 ms on /500 ms off 0 1 1 0 0 Same tone 7 16 35 92 105 113
21 Continuous tone 1000Hz continuous 0 1 0 1 1 Same tone 7 12 19 87 101 106
22 LF Buzz 800-950Hz swept @ 110Hz 0 1 0 1 0 800 cont 7 12 17 86 100 105
23 HF Continuous 2800Hz 0 1 0 0 1 2800 cont 8 17 35 93 106 114
24 Sweep tone (9Hz) 800-970Hz @ 9Hz 0 1 0 0 0 800 cont 7 12 17 86 101 105
25 German DIN tone Sweep 1200-500Hz @ 1Hz 0 0 1 1 1 800 cont 7 11 17 85 100 104
26 Swedish Fire signal Intermittent 660Hz 150 ms on / 150 ms off 0 0 1 1 0 Same tone 6 8 11 82 97 101
27 French tone AFNOR 554Hz for 100 ms and 440Hz for 400ms 0 0 1 0 1 800 cont 6 9 12 83 99 102
28 Swedish all clear signal Continuous 660Hz 0 0 1 0 0 Same tone 6 10 15 83 98 102
2900Hz for 0.5 sec on 0.5 offx3,
off for 1.5 sec then repeat
30 Siren 2 way ramp (short) 500/1200Hz rising then falling 0.25 sec 0 0 0 1 0 800 cont 7 11 15 85 99 103
31 FP 1063.1 - Telecom Alternating tone 800/970 Hz @ 2Hz 0 0 0 0 1 800 cont 7 12 17 86 101 105
32 Siren 2 way ramp (long) 500/1200Hz 3 sec rising / 3 sec falling 0 0 0 0 0 800 cont 7 12 19 87 101 105
29
US Temperal Pattern HF
0 0 0 1 1
2900 cont
1 0 1 1 0
11
Dutch sweep tone
970Hz cont
1 0 1 0 1
Tone table ES1/CS1
10
Australian slow whoop
Intermittent 970Hz 0.625ms on/0.625ms off
Typical Current
(mA)
Typical Sound Output
(dBa)
7
7
18
18
101
106
87
101
8
12
12
12
31
87
92
106
105
113
ES1 (D+E) 1.2