STARTING THE GENERATOR
Before you begin
Observe WARNINGS, CAUTIONS and INSTRUCTIONS contained in this manual and
on plates or decals located on the generator. Do not operate if there is any deficiencies
or irregularities or you do not fully understand the operation of this equipment and any
hazards.
Operator Preventive Maintenance Checks and Services
Check load terminals, sockets and outlets for any irregularities or deficiencies.
Check for any loose hardware, terminal, or fasteners. The starter battery terminals
must be tight.
Insure proper grounding.
Make sure main circuit breaker is in the OFF position
Check air intake cover wing nut for security. Tighten if necessary
Inspect fuel filter assembly for damage and security.
Check fuel filter bowl for water or other contaminants. Inspect fuel system for loose
or missing fuel line clamps, damaged fuel lines, and leaking/damaged fuel tank.
Check for evidence of fuels leaks
Check fuel level and if necessary, service fuel tank to red line on fuel strainer.
Ensure fuel tank fill neck strainer is not clogged or damaged.
If you find any oil in a new generator, it is from factory testing. It must be removed,
engine flushed and replaced with new lube oil.
Ensure generator set is level and check diesel engine lubricating oil level using oil
fill cap/dipstick. Add oil if required.
Inspect the diesel engine and surrounding area for oil leaks.
Inspect cooling fins and air intake slots in recoil starter cover for damage and
debris restricting air flow over and through cooling fins. Remove debris. Check
recoil starter assembly for damage and operation.
AGI6500DE & AGI6500SDE Operator / Owners Manual Version 11.4