Specifications
the engine and generator circuitry are possible sources of ignition. Failure to observe
this warning could result in severe personal injury or death.
1. Check that fuel tank has fuel and that fuel shutoff valve located on the
filter is positioned to ↓O (open).
2. Open two bleed screws at top of filter in the order listed below.
(a) Open left bleed screw to bleed air from tank-to-filter fuel line.
(b) Open right bleed screw to bleed air from filter to pump fuel line. It may
be necessary to squeeze line by hand to force air out of bleed screw.
3. When fuel flows freely and evenly out of bleed screws (without air
bubbles), tighten both bleed screws.
4. Loosen output fuel line fitting at fuel injection pump, place engine RUN
lever to RUN position, depress and hold decompression lever, and pull
recoil starter rope until fuel flows from around fuel line fitting (without air
bubbles). Tighten output fuel line. If you have an electric start version you
can crank the engine for short periods of time to do the same thing.
AGI6500DE & AGI6500SDE Operator / Owners Manual Version 11.4