Specifications

DETAILED PREVENTIVE MAINTENANCE
PROCEDURES
Fuel Filter Replacement
Removal
1. Shut down the generator set
2. Close the fuel shut off valve
3. Unscrew the retaining ring and separate the bowl and head using care not to spill
diesel fuel trapped in the bowl. Then pour diesel fuel into suitable container
4. Remove and discard fuel filter element and gasket
Installation
1. Clean bowl with clean cloth
2. Install new fuel filter element in bowl.
3. Lubricate new gasket with clean diesel fuel and seat in land of bowl
4. Assemble bowl to head and hand-tighten retaining ring
5. Prime and bleed the fuel system
AGI6500DE & AGI6500SDE Operator / Owners Manual Version 11.4