Legal Information First English printing, October 2002 Information in this document has been carefully checked for accuracy; however, no guarantee is given to the correctness of the contents. The information in this document is subject to change without notice. We are not liable for any injury or loss that results from the use of this equipment. Safety Instructions Please read all of these instructions carefully before you use the device. Save this manual for future reference.
F-33.9 Door mount Fan Panel is typically installed on the outside of a cabinet’s rear perforated door to improve extraction of heat from high density cabinet. The unit can be attached to most 42U or taller cabinets. If aisle is relatively narrow for exterior mounting, the unit may be installed on the inside of the perforated door. For details, please refer to the model table below : Front Door Cool Air In Model F-33.9A F-33.
Caution - Power off the fans if the door is to be opened for maintenence or service of items within the cabinet. The fans have finger guards but care must be excerised when working around spinning fans. Keep hair, fingers and other small objects away from the spinning blades. UM-IC-Basic-33U-Q215V1 P.2 www.austin-hughes.
Installation steps The weight of the unit is less than 5kg, so in most cases, holes in perforated cabinet doors can be used to mount the unit. 1 Lift the unit to the desired position. 2 Place attached 6 screws then through the door and tighten them. 3 To eliminate bypass air to maximize heat removal from the cabinet, cut the air blocking material to the size necessary with cutter or scissors then apply the material to the inside surface of the door with screws or adhesive backing.
Hanging bracket installation 1 Assemble & adjust the hanging bracket with M4*6mm screw & nut, to fit the thickness of the door. 2 Install the hanging bracket kit on the rear side of the fan panel with M4*10mm screw. 3 Hang the unit on the door. 4 Place attached 4 screws then through the door and tighten them. 5 Follow steps 3 - 5 on P.3 .
Dimensions F-33.9 195 38.4 1466 UM-IC-Basic-33U-Q215V1 P.5 www.austin-hughes.
Specifications Fan F-33.9 No. of Fans : 9 Individual Fan CFM : 108 CFM Unit CFM ( approx. ) : 972 CFM MTBF : 50,000 hrs Environmental Operating : 0 to 50°C Degree Storage : Relative humidity : Shock : Vibration : -5 to 60°C Degree 5~90%, non-condensing 50G peak acceleration ( 11ms, half-sine wave ) 58~100Hz / 0.98G ( 11ms / cycle ) Weight Net / Gross : 4.6 kgs ( 10.1 lbs ) / 6.9 kgs ( 15.