Owner manual

www.austin-hughes.comUM-IGM-03-Q314V1
P.70
Replacement, Removal Or Addition For EC Box
1. How to replace the failed Master EC Box with a new one ?
Step 1 - Prepare a new Master EC Box and set it to 1st level.
( Please refer to user manual < 1.5 > for details )
Step 2 - Congure the IP address of the new Master EC Box as the failed one
( Please refer to user manual < 4.2 > for details )
Step 3 - Disable alarm email in < Alarm > page
Step 4 - Power off and remove the failed Master EC Box from connection
Step 5 - Install the new Master EC Box to the connection and power it on
Step 6 - Click “ Start Connection “ in < Overview > page for the relevant Master IP group
Step 7 - Congure the new Master EC Box in < EC Box Setting > page such as Name, Location
Step 8 - Enable alarm email in < Alarm > page
2. How to replace a failed certain level slave EC Box with a new one ?
Step 1 - Prepare a new slave EC Box and set the slave EC Box level accordingly
( Please refer to user manual < 1.5 > for details )
Step 2 - Prepare an appropriate length Cat. 5 / 6 cable
Step 3 - Disable alarm email in < Alarm > page
Step 4 -
Use a Cat. 5 / 6 cable to bridge over the failed slave EC Box which will be replaced to minimize
log / data loss
Step 5 - Power off and remove the failed slave EC Box from connection
Step 6 -
Install the new slave EC Box, cancel the cable-bridging and reconnect the slave EC Box to the
previous and next one
Step 7 - Power on the new slave EC Box
Step 8 - Congure the new slave EC Box in < EC Box Setting > page such as Name, Location
Step 9 - Enable alarm email in < Alarm > page
Ignore step 2 and 4 if the failed slave EC Box is in the last level
Part X. Troubleshooting