Manual

www.austin-hughes.comUM-IPM-02-Q414V3
P. 7
< 1.4 > Temp. / Humidity Sensor Connection & Speci cation
Temp. & Humid. Sensor Temp. Sensor
Part no.
IG - TH01 IG - T01
Temperature
Sensitivity
Range
0 to 80°C ( 32 to 176°F )
Accuracy
±1.0°C typical ( ±2°F ) ±1.5°C ( ±3°F)
Resolution 0.1°C ( 0.2°F )
Response Time 5 to 30 sec
Relative
Humidity
Sensitivity
Range
0 to 100% R.H /
Accuracy 0 to 100, ±8.0% R.H
20 to 80, ±4.5% R.H.
/
Resolution 1% R.H. /
Response Time 8 sec /
Power
Requirement
Voltage 12VDC, powered by sensor port
Current Consumption 20mA
Power consumption 0.24 Watt
Power on indicator Red LED Green LED
Housing Chassis & Cover
plastic
Color
Dark gray
Installation Magnetic base for unrestricted installation
Cable
Cable Length
TH sensor w/ 2m cable ( standard )
TH sensor w/ 4m cable ( option )
T sensor w/ 2m cable ( standard )
T sensor w/ 4m cable ( option )
Cable Speci cation 4-wired 3.5mm to RJ11
Cable Color Black Beige
Environmental
Operating 0 to 80°C Degree
Storage -5 to 80°C Degree
Humidity 0~100%, non-condensing
Dimensions
Product 30L x 25Wx 18H mm
Weight
Net 10g
Compatibility
InfraPower W / WS / Wi / WSi series PDU
InfraSolution X-2000 series
InfraGuard Cabinet sensor system
Safety Regulatory
FCC & CE certi ed
Environmental
RoHS2 & REACH compliant