Caution: this procedure must be performed only by qualified persons.
6.7 Connection Diagram for Single-phase
• *1 A suitable device must ensure that the unit can be electrically isolated from the supply(electromagnetic circuit breaker or
by fuse isolator), this allows the qualified people to work in safety.
• *2 Only for the HB option See par. “Heater break Alarm and SCR short circuit”
• *3 The heat-sink must be connected to the earth.
• *4 Only for the Analog Input option , the analog input isn’t isolated from Aux Supply
a series connection between analogue inputs of the units is not possible.
With AC Aux supply it's not possible connect the zero terminal of Analogue Input to the earth.
With DC Aux supply is not possible to connect the zero of the power supply with the zero of analog input