Specifications
18 4114V104-UK
Signal and sensor error indication without display front
Status of the unit can also be read from the red/green LED in the front of the device. 
Green flashing LED 13 Hz indicates normal operation. 
Green flashing LED 1 Hz indicates sensor error. 
Steady green LED indicates internal error. 
Steady red LED indicates fatal error.
Advanced functions
The unit gives access to a number of advanced functions which can be reached 
by answering “Yes” to the point “adv.set”.
Display setup: Here you can adjust the brightness contrast and the backlight. 
Setup of TAG number with 6 alphanumerics. Selection of functional readout 
in line 3 of the display - choose between readout of analogue output or TAG 
number.
Two-point process calibration: The unit can be process-calibrated in 2 points 
to fit a given input signal. A low input signal (not necessarily 0%) is applied 
and the actual value is entered via 4501. Then a high signal (not necessarily 
100%) is applied and the actual value is entered via 4501. If you accept to 
use the calibration, the unit will work according to this new adjustment. If you 
later reject this menu point or choose another type of input signal the unit will 
return to factory calibration.
Process simulation function: If you say ”yes” to the point “EN.SIM” it is 
possible to simulate an input signal by means of the arrow keys and thus 
control the output signal up or down. When you finalise the point with 3, the 
unit returns to normal mode.
Password: Here you can choose a password between 0000 and 9999 in order 
to protect the unit against unauthorised modifications to the configuration. 
The unit is delivered default without password. If you have locked the unit 
with a password by mistake, you can always open the menu by using the 
master password 2008.
Language: In the menu ”lang.setup” you can choose between 7 different 
language versions of help texts that will appear in the menu. You can choose 
between UK, DE, FR, IT, ES, SE and DK.