Installation manual
Publication 1394-IN002B-EN-P — February 2004
4-10 Troubleshooting Status Indicators
MotFeedback 
NoiseFault
(Ax: Mtr Fdbk Noise)
Excessive noise detected 
on feedback signals.
Poor grounding.
• Check ground clamp connectors.
• Check system module grounding.
MotorOvertemp 
Fault
(Ax: Motor x 
Overtemp)
The motor thermal switch 
was tripped.
Motor overload.
• Allow motor to cool down and investigate 
the cause of the motor overload.
• Motor not sized properly.
OverSpeedFault
(Ax: Overspeed)
Motor velocity exceeded 
the overspeed trip limit.
Axis speed has reached 150% of the maximum 
rated setting. The 100% trip point is dictated by 
the lesser of the user velocity limits or the motor 
maximum speed rating.
• Verify operating parameters.
• Verify application requirements.
DriveOvertemp 
Fault
(Ax: Overtemp)
Axis module temperature 
limit exceeded 
The fan on the system module or an axis module 
failed.
Replace the system or axis module.
The cabinet ambient temperature is above rating. Check the cabinet temperature.
The machine duty cycle requires an RMS current 
exceeding the continuous rating of the controller.
Change the command profile to reduce speed 
or increase time.
The airflow access to the 1394 is limited or 
blocked.
Check airflow and re-route cables away from 
the 1394.
DriveOvercurrent 
Fault
(Ax: Power Fault)
The current through any 
one of the power IGBTs has 
exceeded 300% of the 
1394’s current rating.
The motor lead has shorted.
• Check the motor cable.
• Check the resistance of each power phase 
wire to ground. It should be Mega ohms.
• Make sure ferrite cores are not installed 
on motor power conductors.
The motor is malfunctioning.
• Check the resistance of each motor 
winding phase to case ground with an 
ohm meter. Readings should be in Mega 
ohms.
• Return motor for repairs.
Power IGBTs are malfunctioning. Replace the axis module.
Fault Message
RSLogix (HIM):
Description: Potential Cause is: Possible Resolution is: