Installation manual
Publication 1394-IN002B-EN-P — February 2004
3-4 Connecting Your 1394 SERCOS Interface System
Determining Your Type of 
Input Power
Before you ground or wire your 1394 system you must determine the 
type of power distribution system you will be connecting to for main 
input power. The 1394 system is designed to operate in both 
grounded and ungrounded environments.
Grounded Power Configuration
The grounded power configuration allows you to ground your three-
phase power at a neutral point. The 1394 system module has a factory 
installed jumper configured for grounded power distribution. If you 
determine that you have grounded power distribution in your plant 
you do not need to modify your system.
Figure 3.1
Grounded Power Configuration
Note: The input power terminal designated PE is electrically common 
to the system module single point bond bar.
Status
U
V
W
PE2
W1 
V1 
U1 
DANGER
RISK OF ELECTRICAL SHOCK. HIGH VOLTAGE MAY
EXIST UP TO FIVE MINUTES AFTER REMOVING POWER.
SERCOS System Module
PE1
1326 or MP-Series 
motor power cable
Cable clamp around shield
Bonded cabinet ground bus
Conduit/4-Wire Cable
Ground grid or
power distribution ground
System module 
single point bond bar
Shield