Installation manual
Publication 1394-IN002B-EN-P — February 2004
3-6 Connecting Your 1394 SERCOS Interface System
Setting the Ground Jumper 
in Ungrounded Power 
Configurations
These procedures assumes that you have bonded and mounted your 
system module to the subpanel and that there is no power applied to 
the system. 
Setting the Ground Jumper in 5 and 10 kW System Modules
This procedures applies to 1394C-SJT05-D and -SJT10-D system 
modules. To set the ground jumper for an ungrounded system:
1. Verify that all 24V logic and main input power has been removed 
from the system.
2. Open the system module door.
3. Remove the three control board screws (refer to Figure 3.3 for 
locations).
4. Remove ribbon cable from control board (refer to Figure 3.3 for 
location). 
Note: You should not find it necessary to remove both ends of the 
ribbon cable. Remove only the control board end.
5. Remove the control board for easy access to ground jumpers (pull 
it straight out from system module).
6. Locate the jumper connecting J4 and J5 on the assembly adjacent 
to the control board, and move one end of the jumper from J5 to 
J6 (refer to Figure 3.3 for locations).
7. Re-install the control board. Align the guide pins in the rear of the 
enclosure with the holes in the control board.
8. Re-install ribbon cable into the control board connector.
9. Re-install the three control board screws.
10. Close the system module door.
11. Go to Grounding Your 1394 SERCOS Interface System.
IMPORTANT
If you have grounded power distribution, you do not 
need to set the ground jumper. Go to Grounding 
Your 1394 SERCOS Interface System.