Gasogen 29 - 93kW Wood Fired Boiler User Operating Instructions
Gasogen Contents CONTENTS 1 2 3 4 5 6 Symbols used in this man ual .................................................................................................................................................... 2 Correct use of the appliance ..................................................................................................................................................... 2 Water treatment ................................................................................................
Generali Informations 4. INFORMATION TO BE HANDED OVER TO THE USER BY THE INSTALLER/SERVICE ENGINEER The user or the person in charge has to instructed on the use and operation of his heating system, in particular: § Hand over these instructions to the end user, together with any other literature regarding this appliance placed inside the envelope contained in the packaging. The user has to keep these documents in a safe place in order to always have them at hand for future reference.
Gasogen Operating instructions 6 - OPERATING INSTRUCTIONS 6.1 - STANDARD CONTROL PANEL 32. Working thermostat 41. Main fuse (4A) 42. Boiler thermometer 11. Mains switch 12. Fan switch 13. System pump switch 31. Safety thermostat IMPORTANT! Before connecting the control panel to the mains, check that all the switches are in the ‘0’ position and that the safety thermostat is “on”. Boiler start-up 11 Using this switch you can connect or disconnect the boiler from the mains electricity supply .
Operating instructions With the switch nr. 12 you can connect or disconnect the fan from the mains electrical system. 12 12 13 13 on. With the switch in the ‘0’ position the fan is not switched With the switch in the ‘I’ position the fan is connected to the mains electricity supply but it will not run. It will start running only after the upper loading door has been closed. Note: The upper door is open in order to load the wood and the fan is off.
Gasogen Operating instructions The safety thermostat may intervene in case of boiler overheating. You can avoid this by lowering the working thermostat (see previous point). If the boiler’s safety thermostat intervenes often do not try to relight the boiler yourself. Contact your nearest Unical authorized After Sales Service Centre.
Operating instructions 6.2 - OPTIONAL CONTROL PANEL 11. Mains switch 12. Fan switch 13. System pump switch 18. Test key (chimneysweeper mode) 22. Selector switch (0) wood (I) gas/oil 23. Back-up burner switch 31. Safety thermostat 32. Boiler temperature adjustment (75° ÷ 85°C) 41. Main fuse (4A) 42.
Gasogen Operating instructions Mode selection keys (wood firing mode) With the switch nr. 13 you can connect or disconnect the system pump/boiler load from the mains electrical system. 12 13 With the switch in the ‘0’ position the system pump is not switched on. 12 13 With the switch in the ‘II’ position the system pump is connected to the mains electricity supply. With the switch nr. 12 you can connect or disconnect the fan from the mains electrical system. 12 13 on.
Operating instructions Back-up boiler start-up (gas/oil firing mode) Using this switch you can connect or disconnect the back-up boiler linked to the GASOGEN G3 2S from the control panel . With the switch in the ‘0’ position the back-up boiler is not switched on (green led light off) 11 With the switch in the ‘I’ position the back-up boiler is connected to the mains electricity supply (green led light illuminated) and is ready to fire (wood or gas/oil – refer to following points.
Gasogen Operating instructions Boiler start-up (wood firing mode with automatic switching over to gas or oil firing mode when the wood load has been consumed) Using this switch you can connect or disconnect the back-up boiler linked to the GASOGEN G3 2S from the control panel .
Operating instructions Central heating temperature adjustment 32 The adjustment of the system water’s temperature in the GASOGEN G3 2S boiler is obtained by rotating the knob in position 32 in a clockwise direction to increase the temperature and in an antic-clockwise direction to lower it. The temperature can be adjusted between 75°C minimum and 85°C maximum.
Gasogen Operating instructions 6.3 - CHECKS TO CARRY OUT BEFORE FIRING THE BOILER Before firing the boiler carry out the following checks: - Check that the On-Off gas valve, positioned upstream of the boiler, is in the On position (back-up boiler with burner operating with gas). - Check that any On-Off valves fitted on the flow and return pipes for servicing purposes are in the On position. - Check that any On-Off valves fitted on the cold water inlet for servicing purposes are in the On position.
Operating instructions USEFUL SUGGESTIONS and LOADING ERRORS TO BE AVOIDED 6.5 - COMBUSTION AIR ADJUSTMENT PRIMARY AND SECONDARY AIR ADJUSTMENT - Logs too long do not fall down properly and can cause obstructions. The GASOGEN G3 25/ and 50 2S models are equipped with a fan control box for combustion air (pos. 1), with an air distributor, and with primary (pos. P) and secondary air adjusters. (pos. S). - Logs too short cause irregular air passages, with consequent reduction in output and efficiency.
Gasogen Operating instructions For correct air adjustment it will be necessary to observe the flame through the sight glass, placed on the lower door. The flame will have to occupy about two thirds of the combustion chamber, and will have to quietly lick the lower cradle, without moving the ash too much and without making any noise. The flame must be an orange-pink-white colour, not too transparent and with the centre part veering to light blue.
Operating instructions 6.7 - WARNINGS HOW TO AVOID CORROSION IN THE FIRE WOOD BOX The use of wood with a high moisture content (higher than about 25%) and/or loadings not proportioned to the system’s heat request (long OFF periods with the wood storage full) can cause considerable condensate formation in the fire box’s internal wall. Check, once a week, the internal steel walls of the fire box. They must be covered by a slight layer of opaque coloured, dry tar, with bubbles inclined to break and fall off.
Gasogen Operating instructions 6.9 - SERVICING Danger ! Before servicing the boiler, make sure the boiler and its components has cooled down. Warnings In this case: 1) Check the adjustment of the air setting, according to the instructions given in the paragraph “Combustion air adjustment”.
Operating instructions Every month Check that the by-pass is working correctly. The by-pass is a direct passage between the fire box and the chimney. It is normally closed by a mobile shutter. The by-pass is automatically opened or closed via a pushing rod when the loading door is opened. In this way the smoke accumulated in the firebox is aspirated and sent to the chimney directly.
Gasogen Operating instructions 6.10 - FAULT FINDING WOOD FIRED BOILER WITH STANDARD CONTROL PANEL: Problem: The fan does not start Remedy: - Adjust the working thermostat (pos. 32) to maximum. - Reset the safety thermostat (pos. 31). Problem: - The fan starts, but after 30 minutes it stops; by switching OFF and ON the main switch (pos. 11) it re-starts.
Operating instructions WOOD FIRED BOILER WITH OPTIONAL CONTROL PANEL: Problem: The fan does not start Remedy: - Adjust the working thermostat (pos. 32), turning the knob in a clockwise direction to maximum. - Reset the safety thermostat (pos. 31). If you cannot solve the problem, do no attempt any other interventions and contact an authorized UNICAL After Sales Service. Problem: - The fan starts, but after 30 minutes it stops; by switching OFF and ON the main switch (pos. 11) it re-starts.
Gasogen Spare parts 1 2 3 4 5 GASOGEN G3 25 2S GASOGEN G3 40 2S GASOGEN G3 50 2S 7 9 6 8 10 2 1 2 3 4 5 7 8 9 6 7 8 10 GASOGEN G3 65 2S GASOGEN G3 80 2S 20 2
Spare parts 11 12 13 16 17 15 14 GASOGEN G3 25 2S GASOGEN G3 40 2S GASOGEN G3 50 2S GASOGEN G3 65 2S GASOGEN G3 80 2S 21
Gasogen BOILER MODEL COMPONENT POS. Part n° DESCRIPTION GASOGEN G3 25 2S GASOGEN G3 40 2S GASOGEN G3 50 2S GASOGEN G3 65 2S GASOGEN G3 80 2S m. 1,2 m. 1,45 m. 1,45 m. 1,6 m. 1,6 1 20446 Fibre glass gasket 16x21 2 IMP0010 Grip M8 X X X X X 3 MAN0010 Handle grip X X X X X 4 VOL0010 Handle X X X X X 5 20446 Fibre glass gasket 16x21 m. 1,4 m. 1,65 m. 1,65 m. 1,8 m. 1,8 6 GAM0010 Gasket diam.
51 Assembly Tullamarine Vic 3043 Australia PO Box 356 Tullamarine Vic 3043 Australia Telephone +61 3 9330 3300 Facsimile +61 3 9310 5655 Email sales@automaticheating.com.au www.automaticheating.com.