Instruction manual
Coal-trol Digital™ – Model TS2 THERMOSTAT
Automation Correct LLC
6/2006 R0
www.automationcorrect.com
Page 10
Instruction Manual
DEG F
SETUP
SETUP Menu Operation
Press UP button for Deg.  C or 
the  DOWN  button  for  Deg.  F. 
temperature units.
MIN 4
MENU button
MAX 40
MENU button
Starting from  the Round-Robin 
display,  press  and  hold  the 
MENU button  until SETUP is 
shown on the display.
(2 seconds)
MENU button
TBRN N
DISPLAY ACTION NOTE
DEG C
UP button
DOWN button
Minimum  Stoker  Feed  Value 
Press  UP  button  to  increase 
MIN  feed  rate,  DOWN  to 
decrease MIN feed rate.
MIN  feed  value  cannot  be 
increased  beyond  the  MAX 
feed value.
Maximum  Stoker  Feed Value 
Press  UP  button  to  increase 
MAX  feed  rate,  DOWN  to 
decrease MAX feed rate.
MAX  feed  value  cannot  be 
decreased below the MIN feed 
value.
The  SETUP  menu  is  for  initial  setup  and advanced  features. 
Under normal operation, these setting need not be adjusted..
TBRN Y
Temperature Units 
UP button
DOWN button
Set  to  'Y'  for  Tri-burner  type 
feeders, otherwise set to 'N'.
SETUP is  displayed  for  only  1 
second.
MENU button
S 1154A
SET Time of Day Clock Value
Press  UP  or  DOWN  button  to 
adjust.  Display  shows  'A'  for 
AM, 'P' for PM.
After extended power loss, the 
time  of  day  setting  may  be 
adjusted  without  entry  into 
SETUP menu.
HLF 0
Advanced  setting  that  may 
reduce  temperature  overshoot 
after  a  set  point  change.  The 
Heat  Loss  Factor  nominally 
represents  the  insulation 
quality  of  the  dwelling  the 
thermostat  is  controlling. 
Experimentation  over  a 
number  of  days  may  be 
required. 
HEAT LOSS FACTOR 
   Press UP button to increase, 
DOWN button to decrease. 
'0' = Minimum Heat Loss
'1' = Low Heat Loss
'2' = Medium Heat Loss
'3' = High Heat Loss
Continued on next page