Specifications
50 RSLinx – Training Guide
4. Click on the Data Collection Tab and set the Data Collection mode to Poll Rate and
the rate at 100 mSec (one-tenth of a second).
--See illustrations on the next two pages.--
• Polled Messages data collection mode instructs RSLinx to actively go out on
the network and poll data. If you select Polled, you must also enter a polling
rate in the Poll Rate (mSec) field. The minimum value for poll rate is 1ms,
although actual speed depends on the number of active stations and data
highway traffic.
• Unsolicited data collection mode waits for a message instruction from the
processor to send data to RSLinx.
• Send all unsolicited updates sends unsolicited data to the client regardless of
whether or not the data has changed.