Installation Handbook, AutroFlame X33AF PL Multispectrum IR Flame Detector, 116-P-X33AF/PL/DE, 2005-12-12,
Autronica Fire and Security AS
Page 15
5.4 Start-up Procedure
When installation of the equipment is complete, perform the “Fire
Alarm Test” below.
Allow 20 to 30 minutes for the detector’s heated optics to reach
equilibrium.
5.4.1 Fire Alarm Test
Disable any extinguishing equipment that is connected to the system.
Apply input power to the system
Initiate an oi test. (See “Magnetic oi under Optical Integrity in the
Description section of this manual.)
Repeat this test for all detectors in the system. If a unit fails the test,
refer to the “Troubleshooting” section.
Verify that all detectors in the system are properly aimed at the area to
be protected. (The Q1201C Laser Aimer is recommended for this
purpose.)
Enable extinguishing equipment when the test is complete.