Specifications
Appendix A
Installation Handbook, AutroFlame X33AF PL Multispectrum IR Flame Detector, 116-P-X33AF/PL/DE, 2005-12-12,
Autronica Fire and Security AS
Page 26
X33AF PL PERFORMANCE REPORT – CONTINUED
Response Characteristics:
Very High Sensitivity
Fuel Size
Distance
(feet)
Average Response Time
(seconds)
n-Heptane 1 x 1 foot 210* 11
n-Heptane** 1 x 1 foot 210* 6
n-Heptane 1 x 1 foot 100 3
n-Heptane 6 in.x 6 in. 80 3
Isopropanol 6 in.x 6 in. 70 4
Diesel** 1 x 1 foot 150* 14
Methanol 6 in. x 6 in. 40 3
Methanol 1 x 1 foot 150* 18
Methanol** 1 x 1 foot 150* 7
Methane 30 inch plume 100 3
JP-5** 1 x 1 foot 150* 2
JP-5** 2 x 2 foot 210* 4
JP-5** 2 x 2 foot 100 2
Office Paper
0.5 lb.
19” x 19” x 8” 100 4
Corrugated
Panel
18” x 36” 100 8
* Outdoors test condition
** Pre-burn from ignition
Medium Sensitivity
Fuel Size
Distance
(feet)
Average Response Time
(seconds)
n-Heptane
1 x 1 foot 100 12
n-Heptane
1 x 1 foot 50 2
Diesel**
1 x 1 foot 70 4
Methanol
1 x 1 foot 70 10
Methane
30 inch plume 65 3
Methane
30 inch plume 55 2
JP-5**
2 x 2 foot 100 3
Office Paper
0.5 lb.
19” x 19” x 8” 50 6
Corrugated
Panel
18” x 36” 50 2
** Pre-burn from ignition