Specifications
Appendix A
Installation Handbook, AutroFlame X33AF PL Multispectrum IR Flame Detector, 116-P-X33AF/PL/DE, 2005-12-12,
Autronica Fire and Security AS
Page 27
X33AF PL PERFORMANCE REPORT – CONTINUED
Response characteristics in the presence of false alarm
sources:
Very High Sensitivity
False Alarm Source
Distance
(feet)
Fire Source
Distance
(feet)
Average
Response Time
(seconds)
Sunlight, direct, modulated,
reflected
- 6-inch propane 6 <10
Vibration N/A 3-inch propane 10,5 <10
Radio frequency interference 1 3-inch propane 12 <10
Arc welding, #7014 40 1 x 1 foot n-Heptane 40 4
6 kw heater, modulated 80 1 x 1 foot n-Heptane 80 1
6 kw heater, unmodulated 10 1 x 1 foot n-Heptane 80 2
250 w vapor lamp, modulated 3 1 x 1 foot n-Heptane 80 2
300 w incandescent lamp,
modulated
3 1 x 1 foot n-Heptane 80 7
500 w shielded quartz halogen
lamp, modulated
8 1 x 1 foot n-Heptane 80 2
500 w unshielded quartz halogen
lamp, modulated
8 1 x 1 foot n-Heptane 80 3
1500 w electric radiant heater,
modulated
10 1 x 1 foot n-Heptane 80 5
Two 34 w fluorescent lamps,
modulated
3 1 x 1 foot n-Heptane 80 2,5
Medium Sensitivity
False Alarm Source
Distance
(feet)
Fire Source
Distance
(feet)
Average
Response Time
(seconds)
Sunlight, direct, modulated,
reflected
- 6-inch propane 6 <4
Vibration* N/A N/A N/A N/A
Radio frequency interference 1 6-inch propane 6 <10
Arc welding, #7014 10 1 x 1 foot n-Heptane 40 4
6 kw heater, modulated 60 1 x 1 foot n-Heptane 60 2
6 kw heater, unmodulated 10 1 x 1 foot n-Heptane 60 2
250 w vapor lamp, modulated 3 1 x 1 foot n-Heptane 60 1
300 w incandescent lamp,
modulated
3 1 x 1 foot n-Heptane 60 1
500 w shielded quartz halogen
lamp, modulated
8 1 x 1 foot n-Heptane 60 1
500 w unshielded quartz halogen
lamp, modulated
8 1 x 1 foot n-Heptane 60 1
1500 w electric radiant heater,
modulated
10 1 x 1 foot n-Heptane 60 6
Two 34 w fluorescent lamps,
modulated
3 1 x 1 foot n-Heptane 60 2
* Fire was verified with very high sensitivity only