AutroSafe IFG features input and output modules for dierent applications (monitored alarm loops, servicing relays and LEDs,
control inputs, etc.). The modules have the same format, mount onto the panels’ DIN-mounting rail and plug into one another.
Important note on module capacity.
Each fire alarm panel/controller contains a power supply module BSS-310A and a communication module BSL-310.
The BS-420 and BC-420 panels have space for up to 12 modules totally inside the cabinet.
An Al_Com+ stack can contain up to six loop driver modules (BSD-3xx)
By using AutroFieldBus, an additional Al_Com+ stack (with up to six additional loop driver modules) can be added to the system.
NOTE! The AutroSafe panels are certified with the Al_Com+ modules mounted inside the panel cabinet.
Image Part number Description
Monitored inputs
Monitored outputs
Total inputs
Total outputs
Monitors short circuits
Ensures loop communication
For use in EX zone 2 only
Amplified power output
Maximum per panel
Notes
116-BSB-310A Output module • 0 4 • Requires external 24V
116-BSD-310 Loop driver module – – • • 6/12 Max. 127 loop units
116-BSD-310/N Loop driver module – – • • • 6/12 Max. 127 loop units
116-BSD-311
Loop driver module
H.P.
– – • • • 6/12
Image Part number Description
Monitored inputs
Monitored outputs
Total inputs
Total outputs
Monitors short circuits
Ensures loop communication
For use in EX zone 2 only
Amplified power output
Maximum per panel
Notes
116-BSD-330
BS-100 loop driver
module
– – • • 8
116-BSE-310 Input module • 4 0
116-BSE-320 Input module 8 0
Galvanically insulated
inputs
116-BSJ-310 Output module 0 8
Open transistor
outputs
116-BSS-310A
Power supply
module
4 0
116-BSS-311
Dual power
monitoring module
4 4