Specifications

Autronica Fire and Security AS Autronica Fire and Security AS
1514
PRODUCTS 2014
AutroSafe 4 IFG
Cabinets and racks
Integrated fire and gas (IFG) modules
Image Part number Description
116-BN-342/1
PowerLoop 4-20 mA input unit, rack mounted
A general-purpose PowerLoop interface designed for third-party detectors connected
to the AutroSafe IFG system. The unit has a 4-20 mA input galvanically isolated from
the PowerLoop. 19” 3U rack version, bare PCB with 19” rack front panel, no DC/DC.
Degree of protection: IP20
116-BN-342/2
PowerLoop 4-20 mA input unit, DIN rail mounted
A general-purpose PowerLoop interface designed for third party detectors connected
to the AutroSafe IFG system. The unit has a 4-20 mA input galvanically isolated from
the PowerLoop. DIN rail version, bare PCB in an open DIN rail box, no DC/DC. Degree
of protection: IP20
116-BN-342/EX
PowerLoop 4-20 mA input unit, field mounted
A general-purpose PowerLoop interface designed for third party detectors connected
to the AutroSafe IFG system. The unit has a 24 VDC/400 mA supply output providing
power to the connected detectors, plus a 4-20 mA input galvanically isolated from the
PowerLoop. EEX me version including 9,5 W 24 VDC/DC for external detector power
supply.
Cable entry, PowerLoop: 2 x M25. Cable entry, 4-20 mA input: 1 x M25
Degree of protection: IP66
116-BSD-340/1
PowerLoop driver module, rack mounted
The module has a capacity of up to 15 detectors connected directly with protocol
interface or through interface unit (BN-342/XX). The number of detectors must be
verified by means of a PowerLoop calculator. Up to 31 BSD-340 units can be connected
to one alarm panel through the AutroFieldBus driver (EAU-341). Degree of protection:
IP20
116-BSD-340/2
PowerLoop driver module, DIN rail mounted
The module has a capacity of up to 15 detectors connected directly with protocol
interface or through interface unit (BN-342/XX). The number of detectors must be
verified by means of a PowerLoop calculator. Up to 31 BSD-340 units can be connected
to one alarm panel through the AutroFieldBus driver (EAU-341). Degree of protection:
IP20
116-BSD-340/EX
PowerLoop driver, for hazardous areas, zone 1 and 2, field mounted
The module has a capacity of up to 15 detectors connected directly with protocol
interface or through interface unit (BN-342/XX). The number of detectors must be
verified by means of a PowerLoop calculator. Up to 31 BSD-340 units can be connected
to one alarm panel through the AutroFieldBus driver (EAU-341). Dimensions of entries:
5 x M20, 1 x M25.
Degree of protection: IP66
Cabinets and racks
Part number Description
Dimensions
H x W x D
(mm) Notes
116-UEA-323/1 Cabinet for flush mounting BS-410/-420/BC-420 320 x 320 x 140
116-BT-400/1 Termination cabinet for AutroSafe 4
116-BT-401/B Battery cabinet 2 x 12 V/12 Ah 346 x 195 x 107
116-BT-423/B Battery cabinet 2 x 12 V/27 Ah 152 x 420 x 142
Mounting accessories for cabinets and racks
Module height unit = 44.5 mm. Width unless specified otherwise = 48.3 mm.
Rittal cabinets or equivalent are available on request.
Part number Description
Dimensions
(mm)
Height units
Notes
116-UB-383 19” subrack, Europe w = 160 3
116-UW-1454 Mounting kit for 19’’ cabinet/rack. Front panel. h = 399 9 For BS-420
116-UW-1482 Mounting kit for 19’’ cabinet/rack. Front panel h = 266 6 For BU-BV-420
116-UW-1514
Mounting plate for flush mounting panel front in 19”
cabinet/rack
h = 399 9 For BS-420/-430 and BC-420
116-UW-1516/1 Dummy plate 19” h x w = 128 x 60 3 For BC-440
116-UW-1518 Mounting plate h x w = 622 x 455
For mounting AutroSafe 4 front
panel on double BS-100 cabinet
116-UE-1662 Spacer (between 2 rack mounted panels) h x w = 80 x 137.5