Service manual

AUX Air Conditioner Service manual
4
ASW-H12A+12A4/HS2R-VI
Model No
Items
Indoor Unit A
(System A)
Indoor Unit B
(System B)
Outdoor Unit
Type Wall mounted model Heating pump
Cooling kw 3.2 3.2 /
Dehumidify kg/h 1.2 1.2 /
Heating kw 3.6 3.6 /
Noise level dB(A) 43 43 62
Cooling 2.3 2.3 /
Performance
EER
Heating
W/W
2.4 2.4 /
Power supply φ-V-Hz 1 / 220-240V~/ 50Hz
Cooling 1270 1270 2530
Rated input
Heating
W
1360 1360 2500
Cooling 5.52 5.52 11
Rated current
Heating
A
5.91 5.91 10.87
Length m 2 2 4.8
Supply cord
Class / 250V 10A 250V 10A 400V 25A
Starting Current A 30.5 30.5 /
Electrical Data
Fuse capacity A 3.15 3.15 3.15
Refrigerant/Charge g R407c/1100 R407c/1100 /
Type / Rotary Rotary /
Model / 4KS225EBB 4KS225EBB /
Rated input W 1300/1325 1300/1325 /
Compressor
Overload
Protector
/ Inner Inner /
Heat exchanger Row*Hole 2*12 2*12 2*31
Type Capillary tube
Refrigerating System
Expansion device
Specification(mm)
φ3.0*500+φ3.0*500 φ3.0*500+φ3.0*500
/
Air Volume m3/h 620 620 /
Cooling r/min 1180/1050/950/800 1180/1050/950/800 860 Fan Speed
H/M/L/Q
Heating r/min 1180/1050/950/850 1180/1050/950/850 860
Fan type / Cross flow Cross flow Propeller fan
Fan System
Fan motor output W 19 19 68
Connecting
Pipe
Gas /Liquid OD(mm)*L(mm)
Φ9.52×5000/Φ6.35×5000
Connection
Drainage Pipe OD(mm)*L(mm)
Φ14×780
Suitable area m2 12-21 12-21 /
Net dimensions
(W x H x D)
mm 89.2*29.6*17.6 89.2*29.6*17.6 331*846*901
Others
Net weight kg 10.5 10.5 75
Downloaded from AC-Manual.com Manuals