Owner`s manual
Stove Installation (for qualified installers only) 11
© Travis Industries 100-01260 4121205
Chimney Termination Requirements
• Must have an approved cap (to prevent water from entering).
• Must not be located where it will become plugged by snow or other material.
• Must terminate at least 914mm above the roof and
at least 610mm above any portion of the roof
within 3.04M - see Figure 5.
Figure 5
Outside Air Requirements
• Required for mobile homes & in certain localities (check with local building official)
• Must not be drawn from an enclosed space (garage, unventilated crawl space)
• Requires the outside air kit (sku 99200139 – see “a” below). The outside air kit attaches to the
bottom of the stove (see “c” below).
• Outside air duct must have a rodent screen and rain hood (“b”).
• NOTE: Make sure the center divider under the stove is in the farthest forward position.
Figure 6
Min. 3’ (914mm)
Min. 2’ (610mm)
10’ (3.04M)
Min. 3’ (914mm)
10’ (3.04M)
Min. 2’ (610mm)
a
b
Back of Stove
c