8 Stove Installation (for qualified installers only)
5021214 06210-001 seirtsudnI sivarT ©
Floor Protection Requirements
Floor protection must extend to the sides, rear, and front of the stove (see “Clearances” below for
minimum floor protection).
NOTE
: When installed with reduced-clearance connector, the clearance to the backwall may be less
than the floor protection requirement. In this case the floor protection must extend to the wall.
Floor protection must be a minimum 8mm (3/8”) thick fibre-cement sheet with a thermal conductivity
of 0.25W/degree K (or equivalent).
Stove Placement Requirements
Clearances may be reduced by methods specified in NFPA 211, listed wall shields, pipe shields, or
other means approved by local building or fire officials.
Stove must be placed so that no combustibles are within, or can swing within (e.g., drapes, doors),
914mm)of the front of the stove.
If the stove is placed in a location where the ceiling height is less than 2134mm, additional
requirements may apply (contact your local building official).
Must maintain the clearances to combustibles listed below (drywall, furniture, etc.):
Clearances
The following clearances must be met (see Figure 2)
Clearance Requirements: No Flue Shield With Flue Shield
A* Sidewall to stove 500mm 500mm
B* Backwall to stove 400mm 200mm
C* Cornerwall to stove 500mm 150mm
mm003 mm003 htraeH tnorF D
mm002 mm002 htraeH ediS E
mm251 mm251 htraeH kcaB F
Figure 2
* Clearances to combustible material are according to heater test results using a standard flue kit,
(AS/NZS 2918:2001) fitted with 1 length 900mm deco mesh with a heat shield or 1 length 900mm x
120° stainless steel heat shield as a minimum. Any further enquiries please contact Dragon
Wholesaling Pty Ltd on 1800 064 234.