8 Stove Installation (for qualified installers only)
5021214 06210-001 seirtsudnI sivarT ©
Floor Protection Requirements
• Floor protection must extend to the sides, rear, and front of the stove (see “Clearances” below for
minimum floor protection).
NOTE
: When installed with reduced-clearance connector, the clearance to the backwall may be less
than the floor protection requirement. In this case the floor protection must extend to the wall.
• Floor protection must be a minimum 8mm (3/8”) thick fibre-cement sheet with a thermal conductivity
of 0.25W/degree K (or equivalent).
Stove Placement Requirements
Clearances may be reduced by methods specified in NFPA 211, listed wall shields, pipe shields, or
other means approved by local building or fire officials.
• Stove must be placed so that no combustibles are within, or can swing within (e.g., drapes, doors),
914mm)of the front of the stove.
• If the stove is placed in a location where the ceiling height is less than 2134mm, additional
requirements may apply (contact your local building official).
• Must maintain the clearances to combustibles listed below (drywall, furniture, etc.):
Clearances
• The following clearances must be met (see Figure 2)
Clearance Requirements: No Flue Shield With Flue Shield
A* Sidewall to stove 500mm 500mm
B* Backwall to stove 400mm 200mm
C* Cornerwall to stove 500mm 150mm
mm003 mm003 htraeH tnorF D
mm002 mm002 htraeH ediS E
mm251 mm251 htraeH kcaB F
Figure 2
* Clearances to combustible material are according to heater test results using a standard flue kit,
(AS/NZS 2918:2001) fitted with 1 length 900mm deco mesh with a heat shield or 1 length 900mm x
120° stainless steel heat shield as a minimum. Any further enquiries please contact Dragon
Wholesaling Pty Ltd on 1800 064 234.