12 Installation (for qualified installers only)
Travis Industries
100-01136 4040809
Approved Venting Configurations with a Horizontal Termination
• If using a Snorkel Termination (14” or 36”) add the snorkel height to the vertical height (snorkel
terminations are used primarily for basement installations).
• The termination must fall within the shaded area shown in the chart. Use restrictor position #1.
Natural Gas (NG)
Installations
Propane (LP)
Installations
5 feet
0 feet
10' (max)
0 feet
5 feet
0 feet
0 feet
NOTE:
Horizontal sections
require a 1/4" rise every
12" of travel.
12 feet
(max)
NOTE:
A minimum 2 foot rise is required
directly off of the stove.
12 feet
(max)
5 feet
10' (max)
5 feet
Use Restrictor Position # 1
(all shaded areas)
5 feet
0 feet
11' (max)
0 feet
5 feet
0 feet
0 feet
NOTE:
Horizontal sections
require a 1/4" rise every
12" of travel.
NOTE:
A minimum 3 foot rise is required
directly off of the stove.
12 feet
(max)
11' (max)
5 feet
Use Restrictor Position # 1
(all shaded areas)
12 feet
(max)
5 feet