ADPRO FastTrace, Issue 5 2 - 53
2.3.5.1 Temperature Monitor
There is an option present to enable the reporting of a high temperature event to Video Central and to activate the
FastTrace fault relay. The default selection is OFF.
If High Temperature Management is enabled:
When the internal temperature of any disk drive rises above the high temperature threshold, FastTrace will initiate an
over-temperature condition and report this to Video Central. The FastTrace fault relay will activate during the over-
temperature condition. The FastTrace will continue to operate normally after reporting the over temperature condition
but urgent action must be taken to ensure that the ambient temperature complies with FastTrace's 40°C maximum
operating temperature specification. Continued operation at a temperature exceeding the specified maximum may
damage or reduce the useable life of FastTrace.
When the temperature falls below the low temperature threshold, the over-temperature condition will be cleared and
the fault relay will de-activate.
If High Temperature Management is disabled:
No over-temperature alarm will be received by Video Central and the fault relay will not activate for an over-
temperature condition. The unit will continue normal recording.