Figure 18 - Equipment Shutoff Valve
Open
Closed
Equipment
Shutoff Valve
Test Pressures Equal To or Less Than 1/2 PSIG (3.5 kPa)
1. Close equipment shutoff valve (see Fig-
ure 18).
2. Pressurize supply piping system by either
using compressed air or opening gas sup-
ply valve.
3. Check all joints from gas supply (see Fig-
ure 19 or 20) to equipment shutoff valve.
Apply a noncorrosive leak detection uid
to all joints. Bubbles forming show a leak.
4. Correct all leaks at once.
PRESSURE TESTING HEATER GAS CONNECTIONS
5. Correct all leaks at once.
6. Light heater (see Lighting Instructions on
page 18). Check all other internal joints
for leaks.
7. Turn off heater (see To Turn Off Gas Ap-
pliance, page 19).
1. Open equipment shutoff valve (see Fig-
ure 18).
2. Open gas supply tank valve.
3. Make sure control knob of heater is in the
OFF position.
4. Check all joints from equipment shutoff
valve to control valve (see Figure 19 or
20). Apply a noncorrosive leak detection
uid to all joints. Bubbles forming show a
leak.
Gas Valve
Gas Valve
Equipment
Shutoff Valve
Equipment Shutoff Valve
Propane/LP
Supply Tank
Figure 19 - Checking Gas Joints for
Propane/LP Gas
Figure 20 - Checking Gas Joints for
Natural Gas
Gas Meter
(Regulator
supplied by
gas company)
INSTALLATION