58 DSView Installer/User Guide
4. Click OK to save your changes and close the dialog box. A confirmation dialog box displays.
5. Click Yes to save your changes.
- or -
Click No to cancel the operation.
To set the state for outlets on an SPC device:
1. In the DSView management software window topology view, right-click on an SPC device and
then select the Power Management menu item. The Power Management dialog box
will appear.
2. For each SPC device outlet you wish to modify, do one of the following:
•Click On under Status to turn the SPC device outlet on.
•Click Off under Status to turn the SPC device outlet off.
•Click Reboot to reboot the SPC device outlet. If a CPS appliance port is attached to the
SPC device or a DS appliance port is attached to the CPS appliance, it will be rebooted
also. The SPC device’s On or Off state will remain the same as the last time the Power
State dialog box was accessed. Clicking Reboot on an SPC device outlet that is off will
turn the SPC device outlet on immediately. Clicking Reboot on an SPC device outlet that
is on will turn it off, delay, and then turn the SPC device outlet back on.
•Click On under Wake-up State to wake up the SPC device outlet from its sleep state when
meaningful data is detected (such as an Administrator request, or network traffic targeted
to a server).
•Click Off under Wake-up State to disable the waking up of the SPC device outlet. The
wake-up state indicates the state that the port will go into when the SPC device is powered
up during normal operation or when power is restored after an outage. When power is first
supplied to the SPC device, all outlets are initially off. The ports are then sequenced on in
2-second increments. Outlets set to a wake-up state of OFF will remain off, while outlets
set to a wake-up state of ON will be turned on.
3. Click OK to save your changes and close the dialog box. A confirmation dialog box displays.
4. Click Yes to perform the specified SPC device operation.
- or -
Click No to cancel the operation.
Changing the System Settings
Depending on the level of security that you require, certain settings may be configured via the use
of the DSView management software Global Settings dialog box. These options may be accessed
by selecting the Options - System Settings command or clicking the System Settings toolbar icon,
which displays a dialog box with seven tabs: Connections, Polling, Update, Audit Log, Local
Options, Debug and User Names.