POWER AVAILABILITY GXT2-6000RT208™ USER MANUAL 120/208V 120/240V
TABLE OF CONTENTS IMPORTANT SAFETY INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 1.0 GLOSSARY OF SYMBOLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 2.0 INTRODUCTION AND SYSTEM DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 3.0 SYSTEM DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8.0 CONFIGURATION PROGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 8.1 GXT2-6000RT208 Configuration Program Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 8.1.1 What You Will Need . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 8.2 Configuration Program—Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
10.0 MODES OF OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 10.1 Normal Mode Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 10.2 Battery Mode Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 10.3 Battery Recharge Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
FIGURES Figure 1 Figure 2 Figure 3 Figure 4 Figure 5 6 kVA Dual Inverter GXT 2U (front and rear views) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Support base and spacers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 30A branch circuit breaker connection diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Factory default settings for 120VAC UPS . . . . . . . . . . . . .
IMPORTANT SAFETY INSTRUCTIONS ! WARNING Opening or removing the cover may expose you to lethal voltages within this unit even when it is apparently not operating and the input wiring is disconnected from the electrical source. Observe all cautions and warnings in this manual. Failure to do so may result in serious injury or death. Refer all UPS and battery service to qualified service personnel. Do not attempt to service this product yourself. Never work alone.
When replacing batteries, replace with the same Liebert authorized replacement battery kits. ! CAUTION ! CAUTION Do not dispose of battery or batteries in a fire. The battery may explode. Do not open or mutilate the battery or batteries. Released electrolyte is harmful to skin and eyes. It may be toxic. A battery can present a risk of electrical shock and high short circuit current.
Glossary of Symbols 1.
Introduction and System Description 2.0 INTRODUCTION AND SYSTEM DESCRIPTION Congratulations on your choice of the Liebert UPStation GXT2-6000RT208 Uninterruptible Power Supply (UPS). It provides conditioned power to microcomputers and other sensitive electronic equipment. Upon generation, AC power is clean and stable.
System Description 3.0 SYSTEM DESCRIPTION Dynamic Bypass Input L1 L2 N TVSS & EMI/RFI Filters Output L1 Rectifier /PFC Inverter L2 N DC to DC Converter Battery Charger Battery G 3.1 G Transient Voltage Surge Suppression (TVSS) and EMI/RFI Filters These UPS components provide surge protection and filter both electromagnetic interference (EMI) and radio frequency interference (RFI). They minimize any surges or interference present in the utility line and keep the sensitive equipment protected.
System Description 3.5 DC to DC Converter The DC to DC converter utilizes energy from the battery system and raises the DC voltage to the optimum operating voltage for the inverter. This allows the inverter to operate continuously at its optimum efficiency and voltage, thus increasing reliability. 3.6 Battery The UPStation GXT2-6000RT208 utilizes valve-regulated, nonspillable, flame retardant, lead acid batteries.
Major Components 4.0 MAJOR COMPONENTS The GXT2-6000RT208 is composed of three major assemblies to provide easier handling, installation and versatility. 4.1 Main Frame and Electronics This 4U cabinet arrives without internal batteries to lighten the UPS for easier installation. Once the cabinet has been placed in its final floor or rack position, the internal batteries may be installed. The UPS is shipped with a basic hardwire distribution box.
Major Components 4.3 Removable Power Distribution Box The UPS is shipped with a basic hardwire power distribution pack installed. For maximum flexibility, this may be easily replaced with either of two optional power distribution boxes that provide the benefits of hardwire input and output plus manual bypass switch or plug/receptacle convenience with manual bypass switch. DISCONNECT BYPASS POWER TO THE MANUAL BYPASS SWITCH.
What’s Included 5.
Installation and Configuration 6.0 INSTALLATION AND CONFIGURATION This section includes instructions on how to install, configure and perform initial electrical checks of your UPS installation. DO NOT attempt to start the UPS, turn on any circuit breaker or energize the input power until instructed to do so in 7.0 - Initial Startup and Electrical Checks. Visually inspect the UPS for freight damage. Report damage to the carrier and your local dealer or Liebert representative.
Installation and Configuration 6.1.2 Installing the Adjustable Rack-Mount Kit—Sold Separately This kit contains parts needed to mount several different models of UPS and external battery cabinets into EIA310-D standard four-post racks that are 18-32" deep (457-813mm). The weight limit per pair of adjustable rack-mounting brackets is 200 pounds (91 kg).
Installation and Configuration 4. Get eight (8) M4 screws and eight (8) M4 nuts from the hardware pack in this kit. Each nut has a locking, nylon insert that begins gripping the screw when it is halfway tight. Make sure to tighten the nut and screw completely to ensure locking action.Fasten the rear member and the front member together using (4) screws and (4) nuts per bracket assembly as shown in at right.
Installation and Configuration External Battery Cabinet Installation Optional Liebert external battery cabinets may be connected to the UPS to provide additional battery run time. External battery cabinets are designed to be placed on one side of the UPS or stacked beneath the UPS. ! ! CAUTION The external battery cabinet(s) are heavy (see 14.0 - Specifications). External battery cabinets can be used in rack-mount or tower configuration. Take proper precautions when lifting them.
Installation and Configuration 6.3 Connect Input/Output Power The UPS ships with the basic hardwire box attached. If an optional model is to be used, remove the standard box and install the optional box using the three captive mounting screws marked in the illustration, below, right. 6.3.1 Replacing a power distribution box Whenever a power distribution box is not attached to a UPS, the cover must be slid over the electrical connectors to prevent damage or injury. 6.3.
Installation and Configuration 6.3.3 PD-HDWR and PD-HDWR-MBS Terminal Block Connections Conduit entry holes are provided on the rear and side of the box. Input and output wiring should not share the same conduit. Table 1 Electrical requirements—PD-HDWR and PD-HDWR-MBS Input Current Rating Recommended (Max.
Installation and Configuration 6.4 Install the Grounding Electrode Conductor A Grounding Electrode Conductor must be attached to the rear panel using the M5x12 Phillips screw provided. This connection is required in addition to the power input ground connection to the removable power distribution box.
Initial Startup and Electrical Checks 7.0 INITIAL STARTUP AND ELECTRICAL CHECKS Initial Startup and the Configuration Program—The UPS ships with a default 120 VAC L-N setting. This is also the most robust setting in that it can operate with either input phase angle (120 or 180 degrees). Perform initial system checks first. If the UPS configuration needs to be modified for your application, then go to the next section to review use of the configuration program.
Initial Startup and Electrical Checks 7.1 L14-30P Plug-in Connections—Including the PD-001 Distribution Box ! WARNING Miswiring power to the input (L1-L2-N-G) or connecting to single phase voltages (L-N-G only) may damage the UPS. A qualified electrician should verify that the L14-30R is properly wired before attaching the UPS. If the configuration program has been used to set the L-N voltage at 100, 110 or 115, then the input phase angle is required to be 180 degrees.
Configuration Program 8.0 CONFIGURATION PROGRAM The final step of installation may require custom configuration of your UPS using the enclosed configuration program. Some configuration settings may be changed only while the UPS is off. These should be set before the UPS is put into full time service powering the critical load. For most users operating with 120 VAC L-N and with no external batteries, the factory default settings will be adequate.
Configuration Program 8.2 Configuration Program—Installation An easy-to-use installation program will streamline the installation of the configuration program. If you have a previous version of this configuration program installed, it is recommended that it be uninstalled using its Uninstall program before installing this updated version. 1. Use the Windows Explorer to find and open the Lbt_gxt2-1.6.exe installation program on the included software CD. 2. When you see this PreSetup window, select OK.
Configuration Program 8.3 Establishing Communication Link with the UPS Use only the serial communication cable supplied with the configuration program. If an accessory communication card has been installed in the UPS’s communication card slot, the option card must be removed while using the configuration program. Use the serial communication cable to connect your computer’s COM1 port to the DB-9 communication port on the rear of the UPS. COM2 may also be used.
Configuration Program 8.4 Configuration Program—Operation 8.4.1 Read/Confirm UPS Configuration Settings The UPS settings may be monitored, but not changed, using the configuration program while the UPS is operating in any mode. If the program is only used to read the present UPS settings, close the program using the CANCEL button. Mistakenly using the APPLY or OK button will attempt to write data to the UPS and will result in the error message shown at right if the UPS is not off.
Configuration Program 8.5 UPS Tab When the program starts, the following window will open displaying the UPS model along with the current UPS settings. This information can be updated at any time using the REFRESH button. Figure 4 8.5.1 Factory default settings for 120VAC UPS Output Voltage The Output Voltage displayed is the nominal input/output voltage. This is not a voltmeter and will display the nominal voltage whether the UPS is on or off.
Configuration Program 8.5.4 Frequency Selection The UPS is normally designed for 50Hz or 60Hz operation. The factory default corresponds to the model. All models are capable of being used as 50Hz or 60Hz systems. The UPS will automatically sense the utility frequency when first plugged in and set the nominal frequency to match. Therefore, for all normal use the Auto Sense button should be selected. Some special applications require that the UPS be used as a frequency converter.
Configuration Program 8.7 Options Tab Used With Earlier GXT 2U Models This version of the configuration program will accompany GXT 2U UPS models that support new programming features accessible using the Options tab. If version 1.6 (or later) is used with an earlier GXT 2U model (with an earlier UPS firmware version), the Any Mode Shutdown features cannot be changed.
Configuration Program 8.8 Battery Tab Factory default settings illustrated. The boxes on the right show the available options using the drop-down selection boxes. 8.8.1 Low Battery Time Warning The UPS will estimate remaining operating time when on batteries. A low battery alarm is activated if the estimated time reaches the Low Battery Time. This may be changed to any value from 2 to 30 minutes. 8.8.2 Auto Battery Test Time The UPS performs an automated battery test periodically, if enabled.
Configuration Program 8.9 About Tab The version number of the configuration program may be confirmed using the About Tab.
Controls and Indicators 9.0 CONTROLS AND INDICATORS All indicators lit for illustrative purposes. L1 L2 BYPASS Vertical overlay for tower installation UPS ON ! BATTERY AC INPUT -+ UPStation GXT Horizontal overlay for rack mounting 9.1 ON/Alarm Silence/Battery Test Button This button controls output power to connected load(s) and has three functions: • ON • Alarm Silence • Manual Battery Test ON - Pressing this button will start up the UPS in order to provide conditioned and protected power.
Controls and Indicators 9.3 L1 & L2 Load Level Indicators (Two Rows of Indicators: 4 Green, 1 Amber) The Load Level indicators display the approximate electrical load placed upon both output legs of the UPS at all times. Each indicator represents an approximate 25 percent increase in load. For optimum utilization of the UPS, distribute L-N loads to approximately balance the loads on L1 and L2. 9.
Modes of Operation 10.0 MODES OF OPERATION 10.1 Normal Mode Operation During normal operation, utility power provides energy to the UPS. The filters, power factor correction circuit and the inverter process this power to provide computer grade power to connected loads. The UPS maintains the batteries in a fully charged state. The four green Load Level indicators display an approximate level of load in 25% increments.
Communications 11.0 COMMUNICATIONS 11.1 Communications Interface Port The UPStation GXT2-6000RT208 UPS has a standard DB-9 serial port female connector located on the rear of the UPS unit.
Communications 11.2 Pin 4 - Remote Shutdown on Battery 1. This pin is functional only when the UPS is in battery mode. If the UPS is being powered by the utility, Pin 4 will ignore any signal on this pin. 2. Pin 4 requires a 5-12 VDC signal to shutdown. This normally comes form the serial port using Liebert’s contact closure cable. It cannot be used with just a contact closure unless the relay is used to switch a voltage source. A 5-12 VDC signal for 1.
Communications 11.4 Remote Emergency Power Off The UPS is equipped with a Remote Emergency Power Off (REPO) connector. The user must supply a means of interfacing with the REPO circuit to allow disconnecting the UPS input feeder breaker to remove all sources of power to the UPS and connected equipment to comply with national and local wiring codes and regulations.
Maintenance 12.0 MAINTENANCE The UPStation GXT2-6000RT208 requires very little maintenance. The batteries are valve-regulated, non-spillable, flame retardant, lead acid and should be kept charged to obtain their design life. The UPS continuously charges the batteries when connected to the utility supply. When storing the UPS for any length of time, it is essential to plug the UPS in for at least 24 hours every four to six months to ensure full recharge of the batteries.
Maintenance 12.2 UPS Replacement When using a power distribution box with bypass, the UPS can be removed while powering the load through the Bypass Switch. NOTE During the procedure, the connected load will not be protected from power disturbances, such as spikes, sags and failure. To remove the UPS without shutting off power to the connected load: 1. 2. 3. 4. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. DISCONNECT BYPASS POWER TO THE MANUAL BYPASS SWITCH. 5.
Troubleshooting 13.0 TROUBLESHOOTING The information below indicates various symptoms a user may encounter in the event the UPStation GXT2-6000RT208 develops a problem. Use this information to determine whether external factors caused the problem and how to remedy the situation. 1. The Fault indicator will illuminate, indicating the UPS has detected a problem. 2. An alarm will sound, alerting that the UPS requires attention. 3.
Troubleshooting All audible alarms can be silenced, with the exception of Low Battery, Bypass Reminder and Missing Batteries at Startup alarms. Once silenced, the alarm will not sound again until a new alarm condition is present.
Troubleshooting Table 6 Troubleshooting guide Problem Cause Solution Fault and Bypass indicators and diagnostic indicator B are illuminated. UPS internal DC bus overvoltage. UPS requires service. Contact your local dealer, Liebert representative or the Liebert Worldwide Support Group. Fault and Bypass indicators and diagnostic indicator E are illuminated. UPS inverter fault. UPS requires service. Contact your local dealer, Liebert Representative or the Liebert Worldwide Support Group.
Troubleshooting Using the configuration program, the user may specify the number of GXT2-144VBATT external battery cabinets attached to the UPS. The factory default is programmed for internal batteries only. Table 7 shows estimated run times at different loads.
Troubleshooting 13.1 Auto-Learning Battery Run Times As batteries age, the estimated run times may become less accurate. The GXT2-6000RT208 is programmed to “learn” from a full battery discharge and modify the estimated run time for the measured battery capacity. This can improve accuracy and compensate for aging batteries or batteries that operate at different ambient temperatures. The UPS will update the anticipated run time calculation only under certain conditions.
Specifications 14.0 SPECIFICATIONS Table 8 UPS specifications Model Number Model Rating GXT2-6000RT208 4200W/5200VA at 127/220 (120 or 240 degrees only) 4200W/5200VA at 120/208 (120 or 240 degrees) 4200W/6000VA at 120/240 (180 degrees) 4200W/6000VA at 115/230 (180 degrees only) 3780W/5400VA at 110/220 (180 degrees only) 3360W/4800VA at 100/200 (180 degrees only) DIMENSIONS in (mm) Unit W x D x H in. (mm) Shipping W x D x H in.
Specifications Table 8 UPS specifications (continued) Model Number GXT2-6000RT208 ENVIRONMENTAL Operating Temp Storage Temp Relative Humidity Operating Elevation Storage Elevation +32°F to +104°F (0°C to +40°C) +5°F to +122°F (-15°C to +50°C) 0% to 95%, non-condensing Up to 10,000 ft. (3000m) at 104°F (40°C) without derating 50,000 ft.
Specifications Table 11 External battery cabinet specifications Model Number GXT2-144VBATT Used w/ UPS Model GXT2-6000RT208 DIMENSIONS in (mm) Unit (with bezel) W x D x H 3.5 x 24.2 x 17 (87 x 618 x 430) Shipping W x D x H 10.5 x 27.2 x 23 (268 x 692 x 585) WEIGHT lbs (kg) Unit 93.6 (42.5) Shipping 105 (47.6) BATTERY PARAMETERS Type Valve-regulated, non-spillable, flame retardant, lead acid Qty x V x Rating 12 x 12V x 9.
Specifications 44
POWER AVAILABILITY GXT2-6000RT208™ The Company Behind the Products With over a million installations around the globe, Liebert is the world leader in computer protection systems.