Datasheet
Business-Critical Continuity, Emerson Network
Power and the Emerson Network Power logo
are trademarks and service marks of Emerson
Electric Co. ©2009 Emerson Electric Co.
Emerson Network Power.com
Emerson Network Power.
The global leader in enabling
Business-Critical Continuity
™
.
AC Power
Connectivity
DC Power
Embedded Computing
Embedded Power
Monitoring
Outside Plant
Power Switching & Controls
Precision Cooling
Racks & Integrated Cabinets
Services
Surge Protection
Liebert Corporation
1050 Dearborn Drive
P.O. Box 29186
Columbus, Ohio 43229
800 877 9222 Phone (U.S. &
Canada Only)
614 888 0246 Phone (Outside U.S.)
614 841 6022 FAX
Via Leonardo Da Vinci 8
Zona Industriale Tognana
35028 Piove Di Sacco (PD)
Italy
39 049 9719 111 Phone
39 049 5841 257 FAX
Emerson Network Power Asia Pacific
29/F, The Orient Square Building
F. Ortigas Jr. Road, Ortigas Center
Pasig City 1605
Philippines
+63 2 687 6615
+63 2 730 9572 FAX
liebert.com
24 x 7 Tech Support
800 222 5877 Phone
614 841 6755 (outside U.S.)
Specifications
While every precaution has been taken to ensure accuracy and
completeness in this literature, Liebert Corporation assumes no
responsibility, and disclaims all liability for damages resulting
from use of this information or for any errors or omissions.
© 2009 Liebert Corporation. All rights reserved throughout
the world. Specifications subject to change without notice.
All names referred to are trademarks or registered trademarks
of their respective owners.
® Liebert is a registered trademark of the Liebert Corporation.
SL-23182 (R09/09) Printed in USA
Model Number GXT3-500RT120 GXT3-700RT120 GXT3-1000RT120 GXT3-1000MT120
Model Rating VA/W 500/450 700/630 1000/900 1000/900
Dimensions: in. (mm)
DxWxH
19.7x16.9x3.4
(497x430x85)
15.4x6.9x8.9
(390x175x225)
Weight: lbs. (kg) 44 (20)
Input AC Parameter
Voltage Range 120VAC nominal; variable based on output load
Frequency 40Hz
~
70Hz; Auto Sensing
Input Power Cord 10 ft. attached w/ NEMA 5-15P plug
Output AC Parameter
Output Receptacles 5-15R x 6
Voltage 110/115/120/127VAC (user-configurable); ±3%
Waveform Sine wave
Battery
Full Load 12 minutes 6 minutes 5 minutes 5 minutes
Half Load 30 minutes 14 minutes 15 minutes 15 minutes
Recharge Time 3 Hours to 90% capacity after full discharge with 100% load till UPS auto-shutdown
Agency
Safety UL 1778, cUL Listed
RFI/EMI FCC Part 15, Class A=CISPR22 Class B
Surge Immunity IEC 62040-2 2nd Ed
Transportation ISTA Procedure 1A
Model Number GXT3-1500RT120 GXT3-2000RT120 GXT3-3000RT120 GXT3-3000RT208
Model Rating VA/W 1500/1350 2000/1800 3000/2700 3000/2700
Dimensions: in. (mm)
DxWxH
19.7x16.9x3.4
(497x430x85)
23.7x16.9x3.4
(602x430x85)
Weight: lbs. (kg) 48.5 (22) 52.9 (24) 61.7 (28) 61.7 (28)
Input AC Parameter
Voltage Range 120VAC nominal; variable based on output load
208VAC nominal;
variable based on
output load
Frequency 40Hz
~
70Hz; Auto Sensing
Input Power Cord 10 ft. attached w/
NEMA 5-15P plug
10 ft. attached w/
NEMA 5-20P plug
10 ft. attached w/
NEMA L5-30P plug
10 ft. attached w/
NEMA L6-20P plug
Output AC Parameter
Output Receptacles 5-15R x 6 5-20R x 6 L5-30Rx1+5-20Rx6 L6-20Rx1+L6-15Rx2
Voltage
110/115/120/127VAC
(user-configurable); ±3%
208/220/230/240 VAC
(user-configurable); ±3%
Waveform Sine wave
Battery
Full Load 5 minutes 4 minutes 4 minutes 4 minutes
Half Load 16 minutes 11 minutes 14 minutes 14 minutes
Recharge Time 3 Hours to 90% capacity after full discharge with 100% load till UPS auto-shutdown
Agency
Safety UL 1778, cUL Listed
RFI/EMI FCC Part 15, Class A=CISPR22 Class B
Surge Immunity IEC 62040-2 2nd Ed
Transportation ISTA Procedure 1A